Charging curves selection
1.
Setting
0
Press the button MODE while turning ON the battery charger by the general switch and release it once the YELLOW LEDS
1
are lighted. At this point only the YELLOW LED corresponding to position "0" remains lighted and both the RED LEDS "V" and
2
"A" start flashing: for 3 seconds in a slow way (1 flash each second) then for 5 seconds in a quick way (5 flashes each
3
second) and it continues like this in a cyclic way:
4
ADJUSTMENT MODE (slow flashing of the LEDS "V" and "A" (1Hz)
5
DATA STORAGE MODE (quick flashing of the LEDS "V" and "A" (5Hz)
6
2.
Adjustment
7
Entering ADJUSTING MODE: press the MODE button until the LED corresponding to the desired adjustment is
lighted. After 3 seconds from the button release You can enter the DATA STORAGE MODE.
8
3.
Data storage
9
Entering DATA STORAGE MODE: press the MODE button to memorize the desired adjustment. The automatic battery
A
charger's start indicates data storage selection has been successful. After 5 seconds from the button release You return to
B
ADJUSTMENT MODE.
C
D
IMPORTANT: by keeping the MODE button pressed for more 5 seconds while turning ON the device, it returns to the initial
E
"default" setting.
F
Alarms (Two-tone audible message)
SET
An two-tone audible message + flashing LED shows that an Alarm situation has occurred (in this case the battery charger stops
supplying current)
Condition
Audible message + RED
flash
Audible message + YELLOW
flash
Audible message + GREEN
flash
Audible message + RED-
YELLOW flash
Audible message + RED-
GREEN flash
Audible message + YELLOW
-GREEN flash
Audible message + RED-
YELLOW-GREEN flash
Thermal Sensor and/or External Indicator
Thermal Sensor and/or External Indicator are Options that have to be connected to the 5 poles socket 180°.
Unless otherwise stated, the compensation of the Battery Voltage in function of the temperature of the Thermal Sensor
is of -5mV/°C for battery cell.
The control range of the Thermal Sensor goes from -20°C to +50°C.
Attention: over +50°C charger goes in alarm and stops charge.
The External Indicator reflects exactly the LED Indicator which is placed on the equipment.
Further information can be found in the description of the Charging Curve.

Auxiliary Contacts

A
B
1
2
1
Section
Function
Description (
When the equipment is switched on,
Mains
the contact Normally Open (NO)
Section 2
Presence
CLOSES and instead the contact
Normally Closed (NC) OPENS.
When the Stop Phase or the No Stop
End of
Phase is reached, the contact
charge or
Normally Open (NO) CLOSES and
Section 1
Trickle
instead the contact Normally Closed
Phase
(NC) OPENS.
D01474-16
Alarm Type
Battery Presence
Battery disconnected or not in conformity. (Verify the connection and the nominal
voltage).
Thermal Sensor
The thermal sensor is disconnected during the re-charge or it is out of working range.
(Verify the connection of the sensor and measure the temperature of the battery).
Timeout
Phase 1 and/or Phase 2 have a duration in excess of the maximal allowed. (Verify
the battery capacity).
Battery Current
Loss of output Current control. (Failure of the control logic).
Battery Voltage
Loss of output Voltage control. (Battery disconnected or failure of the control logic).
Selection
An unavailable configuration has been selected (Verify the selector's position)
Thermal
Overheating of semiconductors. (Verify the fan operation).
AUX
6
4
1
2
3
1
Unless otherwise stated
NG5-NG7-NG9
Description (Action)
Connector
Pin N°
A
1-2
1
B
2
3-4
1
2
3
AUX
4
5
6
)
Nominal current/Max instant current A
Nominal voltage/ Max voltage commutable Vac
Nominal load in AC1 VA
Nominal load in AC15 (230Vac) VA
Single phase engine capacity (230 Vac) Kw
Break power in DC1: 30/110/220 VA
Minimum mW commutable charge (V/mA)
Mechanical length AC/DC cycles
Electrical duration with nominal charge in A1 cycles
Isolation according EN 61810-1 2nd edition
Isolation between coil and contacts (1.2/50 μs) kV
Dielectric rigidness between open contacts Vac
English
Description
Start/stop hardware
GND
Air pump sensor
Air pump contacts
NC (usually closed) Sez. 2
COM (common) Sez. 2
NO (usually open) Sez. 2
NC (usually closed) Sez. 1
COM (common) Sez. 1
NO (usually open) Sez. 1
10/15
250/250
2500
500
0.37
10/0.3/0.12
500 (5/100)
6
—/10×10
100×10³
2.5 kV/2
4
1000