DC-side
Cable diameter for cable fitting
Cable lug dimension w width max
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
AC-side
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Fuse protection for installation provided by customer (max out-
put overcurrent protection)
Fitting for AC connection
Torque for cable fitting
Interfaces
Cable diameter for cable fitting
Torque for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Cable diameter for cable fitting
Torque for cable fitting
Ethernet connection type
Page 20
16 - 28 mm
42 mm
Depending on the ring cable lug
Solar cable
10mm
30 Nm
M40
10 Nm
240mm² (AL or CU)
in accordance with local installation standards
16 - 28 mm
Depending on the ring cable lug
Bore for M10 screw
30 Nm
Cable lug
42 mm
M10
10 Nm
max. 250A
M40
10 Nm
(2x) 8 - 17 mm
4 (M25) 1.5 (M16) Nm
Spring-type terminal
0.25 - 1.5 mm²
(3x) 5 - 10 mm
4 (M25) Nm
RJ45
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanaet 150 TL3