CONTROLLO MECCANICO
RIARMARE LE MOLLE DEI COMANDI DEGLI INTERRUTTORI ED ESEGUIRE LE SEGUENTI OPERAZIONI:.
1.
CHIUDERE GLI INTERRUTTORI "A" E "B" E CONTROLLARE CHE L'INTERRUTTORE "C" NON POSSA ESSERE CHIUSO.
APRIRE GLI INTERRUTTORI "A" E "B" E RIARMARE LE MOLLE DEI COMANDI.
2.
CHIUDERE L'INTERRUTTORE "A" E "C" E CONTROLLARE CHE L'INTERRUTTORE "B" NON POSSA ESSERE CHIUSO.
APRIRE GLI INTERRUTTORI "A" E "C" E RIARMARE LE MOLLE DEI COMANDI.
3.
CHIUDERE GLI INTERRUTTORI "B" E "C" E CONTROLLARE CHE L'INTERRUTTORE "A" NON POSSA ESSERE CHIUSO.
APRIRE GLI INTERRUTTORI "B" E "C" E RIARMARE LE MOLLE DEI COMANDI.
MECHANICAL CHECK
RESET THE CIRCUIT-BREAKERS OPERATING MECHANISM SPRINGS AND PERFORM THE FOLLOWING OPERATIONS:
1.
CLOSE CIRCUIT-BREAKERS "A" AND "B" AND MAKE SURE THAT THE CIRCUIT-BREAKER "C" CANNOT BE CLOSED.
OPEN CIRCUIT-BREAKERS "A" AND "B" AND RESET THE OPERATING MECHANISM SPRINGS.
2.
CLOSE THE CIRCUIT-BREAKERS "A" AND "C" AND MAKE SURE THAT THE CIRCUIT-BREAKER "B" CANNOT BE
CLOSED. OPEN CIRCUIT-BREAKERS "A" AND "C" AND RESET THE OPERATING MECHANISM SPRINGS.
3.
CLOSE CIRCUIT-BREAKERS "B" AND "C" AND MAKE SURE THAT THE CIRCUIT-BREAKER "A" CANNOT BE CLOSED.
OPEN CIRCUIT-BREAKERS "B" AND "C" AND RESET THE OPERATING MECHANISM SPRINGS.
EINSTELLUNG
DIE FEDERN DER ANTRIEBE DER LEISTUNGSSCHALTER WIEDER SPANNEN UND FOLGENDE SCHALTUNGEN AUSFÜHREN:
1.
DIE LEISTUNGSSCHALTER "A" UND "B" SCHLIESSEN UND SICHERSTELLEN, DASS LEISTUNGSSCHALTER "C" NICHT
GESCHLOSSEN WERDEN KANN.
DIE LEISTUNGSSCHALTER "A" UND "B" ÖFFNEN UND DIE FEDERN DER ANTRIEBE WIEDER SPANNEN.
2.
DIE LEISTUNGSSCHALTER "A" UND "C" SCHLIESSEN UND SICHERSTELLEN, DASS LEISTUNGSSCHALTER "B" NICHT
GESCHLOSSEN WERDEN KANN. DIE LEISTUNGSSCHALTER "A" UND "C" ÖFFNEN UND DIE FEDERN DER ANTRIEBE
WIEDER SPANNEN.
3.
DIE LEISTUNGSSCHALTER "B" UND "C" SCHLIESSEN UND SICHERSTELLEN, DASS LEISTUNGSSCHALTER "A" NICHT
GESCHLOSSEN WERDEN KANN. DIE LEISTUNGSSCHALTER "B" UND "C" ÖFFNEN UND DIE FEDERN DER ANTRIEBE
WIEDER SPANNEN.
REGLAGE
REARMER LES RESSORTS DES COMMANDES DES DISJONCTEURS ET EFFECTUER LES OPERATIONS SUIVANTES:
1.
FERMER LES DISJONCTEURS "A" ET "B" ET CONTROLER QUE LE DISJONCTEUR "C" NE PEUT PAS ETRE FERME.
OUVRIR LES DISJONCTEURS "A" ET "B" ET REARMER LES RESSORTS DES COMMANDES.
2.
FERMER LES DISJONCTEURS "A" ET "C" ET CONTROLER QUE LE DISJONCTEUR "B" NE PEUT PAS ETRE FERME.
OUVRIR LES DISJONCTEURS "A" ET "C" ET REARMER LES RESSORTS DES COMMANDES.
3.
FERMER LES DISJONCTEURS "B" ET "C" ET CONTROLER QUE LE DISJONCTEUR "A" NE PEUT PAS ETRE FERME.
UVRIR LES DISJONCTEURS "B" ET "C" ET REARMER LES RESSORTS DES COMMANDES.
CONTROL MECÁNICO
RESTABLECER LOS RESORTES DE LOS MANDOS DE LOS INTERRUPTORES Y EFECTUAR LAS SIGUIENTES OPERACIONES:
1.
CERRAR LOS INTERRUPTORES "A" Y "B", Y CONTROLAR CHE EL INTERRUPTOR "C" NO PUEDA CERRARSE.
ABRIR LOS INTERRUPTORES "A" Y "B", Y RESTABLECER LOS RESORTES DE LOS MANDOS.
2.
CERRAR LOS INTERRUPTORES "A" Y "C", Y CONTROLAR CHE EL INTERRUPTOR "B" NO PUEDA CERRARSE. ABRIR
LOS INTERRUPTORES "A" Y "C", Y RESTABLECER LOS RESORTES DE LOS MANDOS.
3.
CERRAR LOS INTERRUPTORES "B" Y "C", Y CONTROLAR CHE EL INTERRUPTOR "A" NO PUEDA CERRARSE. ABRIR
LOS INTERRUPTORES "B" Y "C", Y RESTABLECER LOS RESORTES DE LOS MANDOS.