Outdoor connections
Insert an easily accessible 16 A C-curve multi-pole mains switch and having a minimum distance between the
contacts of at least 3 mm in the electrical installation of the building.
For electric network power supply input, use double insulation cables.
Network connection
Passing power
supply cables
E
N
G
Fix the equipment to the plate using the
two supplied M5x10 screws
Input for network power
supply connection
Input for connecting to the
activation system
This hook is intended to help the installer when mounting the equipment
at roof.The fog generator can temporarily hang from it to easily place
F 3
(1 L - Phase 230V ~
N
L
(2) Earthing - Input for earthing
(3) N - Neutral 230V ~
Block the power supply cable to the predefined fastening
point using the supplied cable gland
The twisted wires must not be consolidated with a weld in the
points where they are subject to contact pressure.
The TAMPER wires must be installed so that
they do not come into contact with mains-
powered parts, otherwise they must be directly
tubed.
Passing control and
Block the cables to the predefined fastening
points using suitable strips to ensure they do
not come into contact with mains-powered
parts.
and block the lateral screws.
N.B. never leave the fog generator hanging from the
hook B without blocking it with the lateral screws.
- 36 -
signal cables