Rockwell Automation Allen-Bradley PanelView 600 Instrucciones De Instalación página 10

Ocultar thumbs Ver también para Allen-Bradley PanelView 600:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

All manuals and user guides at all-guides.com
10
PanelView 600 Terminals
5. Install the 4 mounting clips (2 on top, 2 on bottom); the ends of the clips slide
into the slots on the terminal. Tighten the clip mounting screws by hand until
the gasket seal contacts the mounting surface uniformly.
6. Alternately tighten the mounting clip screws to a torque of 10 inch-pounds.
Do not over–tighten.
ATTENTION
!
7. Remove the 2 protective labels covering the top vents of the terminal.
ATTENTION
!
41061-004-01(D)
Protective Installation Labels
Tighten mounting clips to a torque of 10 inch-pounds to
provide a proper seal and to prevent potential damage to the
terminal. Allen-Bradley assumes no responsibility for
water or chemical damage to the terminal or other
equipment within the enclosure because of improper
installation.
Remove the protective installation labels covering the top
vents to prevent overheating and damage to the terminal.
Install 4 Mounting Clips:
Top - Left and Right Slots
Bottom - Left and Right Slots

Publicidad

Tabla de contenido
loading

Tabla de contenido