Elko EP TEV-1 Manual De Instrucciones página 3

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-210/2016 Rev.: 2
Characteristics
• two-level thermostat with function "WINDOW" meaning that output is switched
in case the measured temperature is within set range (adjustable in range -20..
+20 °C / -4 °F to +68 °F)
• used as protection against freezing (water-shoots, pavements, drives, pipes, etc.)
heating is on when temperature falls under set upper level (e.g. +5 °C / +41 °F)
and off in case it falls under lower level (e.g. -10 °C / 14 °F, when heating is not able
eff ectively operate)
• thermostat is placed in water-proof box with IP65, which allows installation outside,
with in-built sensor TZ-0 (included in the supply)
• thermostat status is indicated by LED (3colours) under transparent cover
• function monitoring short-circuit and sensor disconnection (break)
• output changeover contact 16 A / SPDT (AC1)
Description
5
7
cos φ ≥ 0.95
Type of load
AC1
Mat. contacts AgNi,
contact 16 A
250V / 16A
Type of load
AC13
Mat. contacts AgNi,
contact 16 A
250V / 6A
1. Device status indication
2. Bottom temperature setting
3. Upper temperature setting
1
4. Terminal for sensor
2
3
5. Terminals for connection of supply
4
voltage and output contact
6. Sensor TZ-0
7. Sleeve for incoming cables
6
M
M
AC2
AC3
uncompensated
250V / 5A
250V / 3A
230V / 3A (690VA)
K
AC14
AC15
250V / 6A
250V / 6A
TEV-1
Thermostat
Symbol
Connection
Function heating
Function cooling
AC5a
AC5a
compensated
x
M
DC3
DC1
24V / 6A
24V / 16A
1 / 2
L
T
°C
T
N
V2 V1
HAL.230V
AC5b
AC6a
800W
x
250V / 3A
M
DC5
DC12
24V / 4A
24V / 16A
EN
AC7b
AC12
250V / 10A
DC13
DC14
24V / 2A
24V / 2A

Publicidad