Configuration
CF14
Parameters
CF15
CF16
CF19
CF20
CF22
CF23
CF24
CF25
CF26
CF27
CF28
CF29
CF30
CF32
CF33
CF34
CF35
CF36
CF37
26/89
PB1 probe configuration (DEW POINT)
0 = Probe absent
1 = NTC temperature
PB2 probe configuration (AIR INLET)
0 = Probe absent
1 = NTC temperature
PB3 probe configuration (AMBIENT)
0 = Probe absent
5 = NTC temperature
PB4 probe configuration (REFRIGERANT CIRCUIT SUCTION)
0 = Probe absent
1 = NTC temperature
ID1 digital input configuration (1S2)
0 = refrigerant circuit thermal protection
ID2 digital input configuration (REMOTE ON/OFF)
3 = remote on/off
ID5 digital input CONFIGURATION (1Q2 – FAN THERMAL PROT.)
1 = Fan thermal protection
N.U:
ID1-MF digital input polarity (1S2)
0 = active with close contact
1 = active with open contact
ID2-MF digital input polarity (REMOTE ON/OFF)
0 = active with close contact
1 = active with open contact
ID3 digital input polarity (1P1)
0 = active with close contact
1 = active with open contact
ID4 digital input polarity (1P3)
0 = active with close contact
1 = active with open contact
ID5 digital input polarity (1Q2 – FAN THERMAL PROTECTION)
0 = active with close contact
1 = active with open contact
PB4 polarity (REFRIGERANT CIRCUIT SUCTION)
0 = active with close contact
1 = active with open contact
Condensate drain valve/s relais polarity(RL4)
0 = active with close contact
1 = active with open contact
Refrigerant pressure value = 4ma
Refrigerant pressure value = 20ma
PB1 probe calibration offset (DEW POINT)
PB2 probe calibration offset (AIR INLET)
PB3 probe calibration offset (AMBIENT)
PB4 probe calibration offset (REFRIGERANT CIRCUIT SUCTION)
Condensate drain unit operation
0 = Always ON
1 = Timed
Condensate drain ON - time
Condensate drain OFF - time
Selection: ° C or ° F
0 = ° C / BAR
1 = ° F / psi
Selection of mains frequency
0 = 50 Hz
1 = 60 Hz
2 = Direct current
Serial address
Remote controller
0 = 4 buttons
1 = 6 buttons
2 = 6 buttons with NTC probe on board
Default controller display
0 = IN / PROBE
1 = OUT / PROBE
2 = IN / rtC
3 = OUT / rtc
Firmware release
Cod. 710.0103.01.01 – Rev.3B – 03.2012
ED – DXL AL
ED
ED
ED
serie
1
1
5
1
0
3
1
4
1
1
1
0
0
1
0
0
bar
30
bar
-1
° C
0
° C
0
° C
0
° C
1
1
Sec
300
Sec
0
2
1
1
0
2.0