Connection of Optional PCB 5
Optional
Thermostat 2
L
N Cool Heat L
Pool
Pump
Error
signal
Zone 2
Pump
Zone 2
Zone 1
room
room
sensor
sensor
Signal inputs
L N =AC230V, Heat, Cool=Thermostat heat, Cool
Optional Thermostat
terminal
Dry contact Vcc-Bit1, Vcc-Bit2 open/short
(System setup necessary)
SG signal
Switching SW (Please connect to the 2 contacts
controller)
Dry contact Open=Heat, Short=Cool (System
Heat/Cool SW
setup necessary)
Dry contact Open=Comp.ON, Short=Comp.OFF
External comp.SW
(System setup necessary)
DC 0~10V (System setup necessary)
Demand signal
Please connect to the DC 0~10V controller.
 
Outputs
Pool pump
AC230V
 
Thermistor inputs
Zone room sensor
PAW-A2W-TSRT
Pool water sensor
PAW-A2W-TSHC
Recommended External Device Specifi cation
This section explains about the external devices (optional)
recommended by Panasonic. Please always ensure to use the
correct external device during system installation.
For optional sensor.
1. Pool water sensor: PAW-A2W- TSHC
Use to detect the water temperature of the control zone.
Mount it on the water piping by using the stainless steel metal
strap and contact paste (both are included).
Dimensions (mm)
35
16
Optional
Mixing
Thermostat 1
valve 2
N Cool Heat
N
O
C
Pool
Zone 2
Demand
Solar
sensor
water
water
signal
sensor
sensor
93
2. Outdoor sensor: PAW-A2W-TSOD
If the installation location of the outdoor unit is exposed to direct
sunlight, the outdoor air temperature sensor will be unable to
measure the actual outdoor ambient temperature correctly.
In this case, optional outdoor temperature sensor can be fi xed
at a suitable location to more accurately measure ambient
temperature.
Dimensions (mm)
46
Ext.
comp.
SW
Heat/
Cool
SW
3. Room sensor: PAW-A2W- TSRT
Install the room temperature sensor to the room which requires
Vcc
SG
room temperature control.
Bit1
signal
Bit2
4. Please refer to the table below for sensor characteristic of the
sensors mentioned above.
Temperature
(°C)
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-30
-35
-40
For optional pump.
Power supply: AC230V/50Hz, <500W
Recommended part: Yonos 25/6: made by Wilo
70
93
Dimensions (mm)
30
86
86
Resistance
Temperature
(kΩ)
(°C)
5.326
150
6.523
140
8.044
130
9.980
120
12.443
110
15.604
100
19.70
90
25.05
80
32.10
70
41.45
65
53.92
60
70.53
55
93.05
50
124.24
45
167.82
40
35
70
60
Resistance
(kΩ)
0.147
0.186
0.236
0.302
0.390
0.511
0.686
0.932
1.279
1.504
1.777
2.106
2.508
3.003
3.615
4.375

Publicidad