1B_I+OM_4PW17551-1B.book Page 10 Wednesday, October 5, 2005 9:18 AM
ECFWER6
INSTALLATION INSTRUCTIONS
Remote type controller

Installation

It is advisable to set the microswitches before installing
the controller, see paragraph "Setting the microswitches"
on page 10.
The remote controller can be installed to a wall.
Proceed as follows to fit the controller.
1
Remove the controller lock screw and remove the
cover.
To facilitate its re-installation, be careful not to
modify the position of the 2 rotating knobs on
the controller cover (operating mode selector
switch
and
thermostat)
corresponding
potentiometers
electronic PCB.
2
Drill 2 holes in the wall where the controller shall be
installed, at the exact same position of the fixing slots
(5 x 8 mm) located on the control base (see figure 9).
3
Make the electric connections to the control terminal
board according to the wiring diagram of the selected
configuration.
4
By means of screws, fix the control base to the wall.
5
Reassemble the control cover part and make sure
the rotating knobs are in the same position as they
were upon disassembly. Secure the controller lock
screw back into place again.
6
Make the electric connections to the unit according to
the wiring diagram of the selected configuration.
When installing the ECFWER6 controller on
units with a current consumption greater than
1 A, you must install an additional EPIMSA6
Master/Slave interface or EPIA6 Power
interface (see "Master/Slave interface and
Power interface" on page 11).
ECFWEB6+ECFWER6
Microprocessor controller for fan coils
S
ETTING THE MICROSWITCHES
1
Unscrew the controller lock screw from the bottom
side of the controller. Remove the front panel of the
controller.
To facilitate its re-installation, be careful not to
modify the position of the 2 rotating knobs on the
controller cover (operating mode selector switch
and thermostat) and of the corresponding
potentiometers fit on the electronic PCB.
2
Arrange
corresponding to one of the configurations explained
(see "Possible configurations" on page 7).
List of microswitches and their functions
(See figure 7)
and
of
the
Micro-
fit
on
the
switch
number Function
cooling/heating
1
switching
cooling/heating
2
switching
automatic cooling/
heating switching
3
mode based on the
temperature of the
range of the neutral
zone for the automatic
4
cooling/heating mode
based on the air
temperature
valve presence on
5
hydraulic circuit
electric heater
6
presence
number of pipes of
7
the hydraulic circuit
if the desired configuration does not include
the electric heaters control function and the
operating mode selector switch is turned to the
electric heater symbol, the fan coil will
continue to run with an automatic fan speed
and will regulate the air temperature by means
of the fan.
4PW17551-1B
the
microswitches
in
the
sequence
Position
OFF
controller
remote
manual
automatic
air
5°C
2
Installation and operation manual
ON
water
2°C
4
10