The low level configuration is necessary to set the parameters of the AC-MAX_CU circuit and must be
performed after the AC-MAX_CU Control Unit is registered in the AC-MAX LT/ST software. During the
first low level configuration the own IP address and the communication key are configured. The
programming of other parameters depends on the requirements of each installation scenario and is not
mandatory.
Low-level configuration procedure (firmware 1.7.2 or higher).
AC-MAX LT/ST v2.0 SOFTWARE is required:
Preliminary configuration includes setting the network parameters of your computer according to the
default settings of the AC-MAX_CU Control Unit. The IP address of the computer must be in the same
subnet, i.e. 192.168.0.xxx.
Also the creation of databases with AC-MAX LT or ST(v2.0) software, configuration of communication
services, detection of controllers. All these steps are explained in the document AC-MAX LT or ST v2.0
Quick Start Guide. The EXP expanders must be detected on the RS-485 bus after connection of the AC-
MAX_CU.
1. Select in the navigation tree under Configuration right-click on Access ControllersAdd
Access Controller with the building icon.
2. Enter the factory default communication parameters, including the IP address and the
communication password.
ONFIGURATION
Default:
IP Address = 192.168.0.213
Communication password = 1234
EN