Integra Xmart Optima-33-T10 10K Manual Del Usuario página 62

Tabla de contenido

Publicidad

08: Bypass mode setting
Interface
09: Maximum battery discharge time setting
Interface
10: Reserved
Interface
11: Hot standby
Interface
USER MANUAL – OPTIMA-33-T10 10K-80K
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on
bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it's not allowed for running in Bypass mode
under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual
bypass is not allowed. Manual bypass means users manually operate UPS for Bypass
mode. For example, pressing OFF button in AC mode to turn into Bypass mode.
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down
to protect battery if the discharge time arrives before the battery is under voltage. The
default value is 990 min.
DIS: Disable battery discharge protection and backup time will depend on battery
capacity.
Setting
WARNING: THIS IS A FUNCTION FOR SERVICE PURPOSES.
IT IS ONLY TO BE USED ONLY BY QUIALIFIED TECHNICIANS.
THIS FUNCTION MUST NOT BE OPERATED BY USERS
This function is used to do a self-test of the unit under special conditions.
Factory set value: DIS = Disable.
Setting
HSH: Hot Standby Function
YES: Function enabled. It allows UPS to restart-up even without batteries connected to
the UPS
NO: Function disable. Ups runs in normal mode. It only can be started with batteries
properly connected to the UPS.
59

Publicidad

Tabla de contenido
loading

Tabla de contenido