Battery disposal and safety
• C aution. Battery service life is reduced by 50 % for every ten degrees above 25 °C (77 °F).
• T he battery must be replaced exclusively by qualified personnel (risk of shock), with new battery approved by
Eaton to ensure correct operation of the UPS.
• T he battery must be disposed of in accordance with applicable regulations. T o remove the battery, shut down the
UPS (button
OFF), remove the power cord and proceed as indicated below "Battery change".
12
Battery change
550 / 700
• Warning: take care not to inverse the polarity + (red) and - (black) when connecting the battery as this will
destroy the device.
Technical characteristics
Eaton 5S
• UPS power
• Nominal input voltage
• Input frequency
• V oltage/frequency of battery backup
outlets
in battery mode
9
• Total output current for all outlets
• O utput current of battery backup
outlets
9
• Leakage current
• Input protection
• Transfer time
• Telephone/Data surge protection
• Sealed lead-acid battery
• Automatic battery test
• Average battery life
• Operating temperature
• Storage temperature
• Operating relative humidity
• Operating elevation
• Safety standards
• E lectromagnetic compatibility
standards
• Dimensions (mm/inch)
• Weigth (kg/lb)
(*) Warning: Output cables should not exceed 10m (32.81 ft) length.
4
All manuals and user guides at all-guides.com
a
Press and slide
4 years typical, depending on temperature and number of discharge cycles
b
550
550 VA /
330 W
93 V - 138 V
50/60 Hz (46 - 70 Hz working range)
115 V +15 % -20 % (60 Hz ± 1 Hz)
10 A max
4.8 A max
0.4 mA
10 A resettable circuit breaker
5 ms typical
Tel, ISDN, ADSL, Ethernet
12 V, 7 Ah
Once a week
0 to 35 °C / 32 to 95 °F
-25 °C to +55 °C / -13 °F to 131 °F
0 to 85 %
0 to 2000 m / 0 to 6562 ft
UL 1778
FCC Part 15 Class B
260 x 87 x 250 / 10.24 x 3.43 x 9.84
5.6 / 12.3
c
700
700 VA /
420 W
6.14 A max
12 V, 9 Ah
6.5 / 14.3
614-06820-01