Led Display; Led 1: Btl Status; Led 2: Profinet Status (Dual Led); Led 3/Led 4: Link/Activity - Balluff BTL7-V50T-M-P-C003 Serie Manual De Instrucciones

Ocultar thumbs Ver también para BTL7-V50T-M-P-C003 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BTL7-V50T-M _ _ _ _ -P-C003
Magnetostrictive Linear Position Sensor – Rod Style
3
Construction and function (continued)
3.3

LED display

LED 4
(Link/Activity
OUT)
LED 1
(BTL status)
Fig. 3-2:
BTL7 LED displays
3.3.2
LED 2: PROFINET status (dual LED)
LED 2
Red
Green
(Bus Failure)
Off
Off
On
On
On
Flashing
1)
Off
On
Flashing frequency is 0.5 Hz. The signal is shown for at least 3 s.
1)
Tab. 3-2:
LED 2
3.3.3
LED 3/LED 4: Link/Activity
LED 3/LED 4
Status
Green
On
Port open
Flashing
Requested by the master
to identify the device
Off
Port closed
Tab. 3-3:
LED 3/4
8
english
LED 3
(Link/Activity
IN)
LED 2
(PROFINET
status)
Meaning
No supply voltage
No bus connection with other
participants (no link)
Bus connection (link) available, but
the sensor is not involved in cyclic
data exchange.
The sensor is involved in cyclic data
exchange.
Connection
Yes
Yes
No
3.3.1

LED 1: BTL status

LED 1
Operating state
Green
Normal function
Magnet is within the limits.
Error
Red
No magnet or magnet outside the limits.
Tab. 3-1:
LED 1
Cause
Bus not connected
Master cannot be accessed or is switched off
Sensor is starting up, but parameterization has not yet been
completed.
Sensor has been incorrectly configured.
The sensor was assigned an incorrect station address and is thus
not accessible.
The desired configuration is not the same as the sensor
configuration.