Introduction
Th is manual refers to refrigeration dryers designed to guarantee high
quality in the treatment of compressed air.
2.1 Transport
Th e packed unit must:
• remain upright;
• be protected against atmospheric agents;
• be protected against impacts.
2.2 Handling
Use a fork-lift truck suitable for the weight to be lift ed, avoiding any type
of impact.
2.3 Inspection
a) All the units are assembled, wired, charged with refrigerant and oil
and tested under standard operating conditions in the factory;
b) on receiving the machine check its condition: immediately notify
the transport company in case of any damage;
c) unpack the unit as close as possible to the place of installation.
2.4 Storage
If several units have to stacked, follow the notes given on the packing.
Keep the unit packed in a clean place protected from damp and bad
weather.
3
Installation
Y
For the correct application of the warranty terms, follow the in-
structions given in the start-up report, fi ll it in and send it back to Seller.
3.1 Procedures
Install the dryer inside, in a clean area protected from direct atmosphe-
ric agents (including sunlight).
In places with fi re hazard, provide for a suitable fi re-extinguishing sy-
stem.
Y
Comply with the instructions given in par. 8.2 and 8.3.
All dryers must be fi tted with adequate pre-fi ltration near the dryer air
inlet. Seller is excluded any obligation of compensation or refund for any
direct or indirect damage caused by its absence
Y
Pre-fi lter element (for 3 micron fi ltration or better) must be repla-
ced at least once a year, or sooner as per manufacturer recommenda-
tions.
Y
Correctly connect the dryer to the compressed air inlet/outlet con-
nections.
3.2 Operating space
Leave a space of 1.5 m around the unit.
English
3.3 Versions
Air-cooled version (Ac)
Do not create cooling air recirculation situations. Do not obstruct the
ventilation grilles.
3.4 Tips
To prevent damage to the internal parts of the dryer and air compres-
sor, avoid installations where the surrounding air contains solid and/or
gaseous pollutants (e.g. sulphur, ammonia, chlorine and installations in
marine environments).
Th e ducting of extracted air is not recommended for versions with axial
fans.
3.5 Electrical connection
Use approved cable in conformity with the local laws and regulations
(for minimum cable section, see par. 8.3).
Install a diff erential thermal magnetic circuit breaker with contact ope-
ning distance 3 mm ahead of the system (RCCB - IDn = 0.3A) (see the
relevant current local regulations).
Th e nominal current In of the magnetic circuit breaker must be equal to
the FLA with an intervention curve type D.
3.6 Condensate drain connection
Y
Make the connection to the draining system, avoiding connection
in a closed circuit shared by other pressurized discharge lines. Check the
correct fl ow of condensate discharges. Dispose of all the condensate in
conformity with current local environmental regulations.
4
Commissioning
4.1 Preliminary checks
Before commissioning the dryer, make sure:
• installation was carried out according that given in the section 3;
• the air inlet valves are closed and that there is no air fl ow through the
dryer;
• the power supply is correct.
4.2 Starting
d) Start the dryer before the air compressor;
e) switch the power on by turning the MAIN SWITCH "
ON» (see par. 5.1 for the meaning of the LEDs);
f) Wait 5 minutes, then slowly open the air inlet valve;
g) slowly open the air outlet valve: the dryer is now drying.
4.3 Operation
a) Leave the dryer on during the entire period the air compressor is
working;
b) the dryer operates in automatic mode, therefore fi eld settings are
not required;
PSH 030-090
c) in the event of unforeseen excess air fl ows, by-pass to avoid overlo-
ading the dryer;
d) avoid air inlet temperature fl uctuations;
e) Condensate draining is factory-set in TIMED mode, with max.
permissible opening equal to10 seconds.
Th e set time can be decreased (see par. 5.2 for details).
4.4 Stop
a) Stop the dryer 2 minutes aft er the air compressor stops or in any
case aft er interruption of the air fl ow;
b) make sure compressed air does not enter the dryer when the dryer
is disconnected or if an alarm occurs.
c) switch off at the MAIN SWITCH "
&
" , to «I
&
".
7