ASC2500G/ASC3500G LE
9
Service tasks
9.1
Calibrating the oil scales
I
NOTE
In order for the oil quantities and the UV additive to be measured
correctly, the zero point of the scales must be checked regularly and
reset if necessary.
Resetting is necessary:
If the quantity in a container deviates by more than 10 ml from the
target value
If the AirConServiceCenter has been shaken, for example during
transport on bumpy roads
Every four to six weeks
1. In the basic menu, use the cursor keys or to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor keys or to select "Reset scales":
4. You are then prompted to remove the containers from the scale:
EN
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Remove the 3 Oil/UV
glasses from scales.
ENTER-OK STOP-EXIT
Service tasks
93