5.
START UP
CACB-N without mounted
electric accessory
M
~
1
2
3
4
C1 C2 C3
Curve
230 V~
choice
N
Ph
50 Hz
Make sure that the assembly rotates freely (fan wheel) and that no object is liable to be ejected by the
turbine. Before getting started, the box must be connected to the network and the cover must be closed.
Make sure that the current absorbed by the motor is not more than 5% above the current indicated (see
data label).
6.
MAINTENANCE
6.1 Maintenance
Cut off the electric power supply before any intervention and make sure that it cannot be switched on again
during the intervention consign (by locking). Remove dust from the fan wheel blades.
6.2 Spare parts
Code
009024
Moto-turbine
009025
Moto-turbine
009026
Motorfan
009027
Motorfan
009028
Motorfan
0000132205
Condenser
0000132206
Condenser
0000132239
Condenser
0000132208
Condenser
0000132209
Condenser
7.
WASTE MANAGEMENT
7.1 Treatment of Packaging and General Industrial Waste (GIW)
The packaging (unconsigned pallets, cartons, films, wooden boxes) and other GIW must be made reu-
sable by an approved service provider. It is strictly prohibited to burn, bury or dump them in nature.
7.2 Treatment of Professional WEEE
This product must not be dumped or treated with household refuse, but must be deposited in an appro-
priate collection point for waste electrical and electronic equipment (WEEE).
CACB-N with switch
remounted
PTO
1
3
N
2
4
PTO
LS
MS
N 230 V~
50 Hz Ph
Type
Quantity
1
1
1
1
1
1
1
1
1
1
3 speed
motor
M
2
~
4
6 8
5
7
6
8
HS
Spare moto-turbine for CACB-N 05
Spare moto-turbine for CACB-N 08
Spare motorfan for CACB-N 12
Spare motorfan for CACB-N 20
Spare motorfan for CACB-N 30
Condenser for CACB-N 05
Condenser for CACB-N 08
Condenser for CACB-N 12
Condenser for CACB-N 20
Condenser for CACB-N 30
13/20
CACB-N with circuit
breaker mounted
PTO
N
HS
Speed choice
Speed 1 : see draw
( white cable on T2 )
230V
Speed 2 : reverse white
50Hz
and brown.
Speed 3 : reverse white
and black.
Name
NT_518736_CACB-N_ES-AN-FR-150528