mabe MMI12CABWCCE8 Manual De Instrucciones página 84

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

84
7. To prevent gas leakage, turn the service port's cap. The valve rod's
cap for 2-way valve and 3 way's a little more than the point
where the torque increases suddenly.
8. After attaching each cap, check for gas leakage around the caps.
Step 2
Open
Step 3
Step 4
Open 90°
2-way valve
2-way valve. Liquid side
3-way valve. Gas side
Step 1
Tubes (for R410A)
Close
2-way Valve
3-way Valve
3-way valve
Gauge manifold
(for R410A)
Anti countercurrent
joint
Vacuum pump
(for R410A)
Step 6
2-way valve
3-way valve
Step 7
2-way valve
3-way valve
Valve
rod cap
Valve
rod cap
Service port cap
CAUTION
• If the refrigerant of the air con-
ditioner leaks, it is necessary to
discharge all the refrigerant.
Vacuum first, then charge the
liquid refrigerant into air condi-
tioner according to the amount
marked on the name plate.
• Please do not let other cooling
medium except the specified
one (R410A) or air enter into
the cooling circulation system.
Otherwise there will be abnor-
mal high pressure in the system
to make it crack and lead to
personal injuries.

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Tabla de contenido