5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
voltage
voltage
14.1
13.8
off
off
28.2
27.6
56.4
55.2
14.4
13.8
off
on
28.8
27.6
57.6
55.2
14.7
13.8
on
off
29.4
27.6
58.8
55.2
15.0
13.8
on
on
30.0
27.6
60.0
55.2
ds6: absorption time 8 or 4 hours (na for L2, L3)
ds5: adaptive charging algorithm (na for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (na for L2, L3)
(the wide input frequency range (45-55 Hz) is 'on' by default)
Note:
-
If "adaptive charging algorithm" is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If "adaptive charging algorithm" is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
Step 2: Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to 'off' and do
not reflect the actual settings in the microprocessor).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Step 2
Example 1 (factory setting):
Example 2:
8, 7 GEL 14,4 V
8, 7 OPzV 14,1 V
6 Absorption time: 8 hours
6 Abs. time: 8 h
5 Adaptive charging: on
5 Adaptive ch.: on
4 Dynamic current limit: off
4 Dyn. Curr. limit: off
3 UPS function: on
3 UPS function: off
2 Voltage: 230 V
2 Voltage: 230 V
1 Frequency: 50 Hz
1 Frequency: 50 Hz
To store the settings after the DIP switches are set according to the required values: press the 'Down' button for 2 seconds (lower
button to the right of the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
The DIP switches can be left in the selected positions, so that the 'other settings' can always be recovered.
Storage
voltage
13.2
Gel Victron Long Life (OPzV)
26.4
Gel Exide A600 (OPzV)
52.8
Gel MK battery
Gel Victron Deep Discharge
13.2
Gel Exide A200
26.4
AGM Victron Deep Discharge
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.2
Tubular plate traction batteries in
26.4
semi-float mode
52.8
AGM spiral cell
13.2
Tubular plate traction batteries or
26.4
OPzS batteries in cyclic mode
52.8
DS-8
off
DS-8
on
DS-7
off
DS-7
DS-6
on
DS-6
on
DS-5
on
DS-5
on
DS-4
off
DS-4
on
DS-3
off
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
on
Step 2
Example 3:
8, 7 AGM 14,7 V
6 Abs. time: 8 h
5 Adaptive ch: on
4 Dyn. Curr. limit: on
3 UPS function: off
2 Voltage: 240 V
1 Frequency: 50 Hz
Suitable for
on = 8 hours
off = 4 hours
on = active
off = inactive
(inactive = fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 230 V
off = 240 V
on = 50 Hz
off = 60 Hz
DS-8
on
off
DS-7
on
DS-6
off
DS-5
off
DS-4
off
off
DS-3
on
off
DS-2
off
DS-1
off
Step 2
Example 4:
8, 7 Tub.-plate 15 V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 240 V
1 Frequency: 60 Hz