Macurco TX-12-AM Manual De Instrucciones página 21

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.
Turn on the regulator to start the gas flow and wait with the gas applied continuously.
6.
With the display function turned "On", the TX-12-AM will show the current concentration of gas or "0" (zero) in clean air. When
the gas concentration reaches the Fan Relay setting (20 ppm, for example) the display will flash back and forth between "FAn"
and "20". With the display function turned "OFF", the display does not show the gas concentration, but will show "FAn" as long
as the fan relay is activated.
Note: If the Fan relay does not close within 2 minutes, there are five possibilities:
a.
Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25psi or less.
b.
Unit needs to be re-calibrated (go through recalibration and re-test).
c.
Detector is in need of servicing (return unit to factory for servicing).
d.
Detector has fan relay set to disable (diS) or higher than 20. Set fan relay to 20 ppm and repeat the test.
e.
Detector has fan relay delay set to 3 minutes. Set fan relay to 0 minutes and repeat the test.
7.
Remove the gas from the sensor. Proceed to Test the Alarm relay or replace the top cover. Fan relay test is complete.
Testing the Alarm Relay
Note: The gas concentration to activate the Alarm relay depends on the setting.
1.
Connect the 25 ppm cylinder of Ammonia to the regulator.
2.
Check the pressure gauge. If there is 25psi or less the cylinder should be replaced.
3.
Place the test hood over the gas sensor. Turn on the regulator to start the gas flow.
21