7.
The TX-6-HS will step through a cycle test:
a.
b.
c.
d.
e.
f.
8.
When testing is completed reassemble the unit or units.
Manual Operation Test
This option gives the user the opportunity to manually initiate an individual test for each relay, the analog output and the sensor
response to gas. From normal operation mode press the Next button 2 times to get to the Test Mode (tSt). Press the Enter button once
to get into the Test Menu. Press the Next button to scroll through the five test options and press Enter to initiate the selected test. Note
that if the relay or 4–20 mA output has been disabled, the test selection will not be displayed in the test menu.
bUZ – Buzzer Test, 3 seconds
Art - Alarm Relay Test, 5 seconds
Frt - Fan Relay Test, 60 seconds
42t - 420 loop test, 130 seconds
gtS - Gas Test, 3 minutes (no output to the panel during the gas test)
The display will flash during the test, or in the case of the gas test, the gas level will alternate with gtS. Once the test is complete, the
display will return to steady display. To exit the test menu, press the Next button until "End" is displayed, then press Enter to return to
normal mode.
Hydrogen Sulfide Gas Test
The following steps must be performed when conducting a calibration or calibration verification test (bump test) to ensure proper
performance of the monitor. Failure to do so may adversely affect product performance and result in sickness or death.
When performing a calibration or calibration verification test (bump test) only use certified calibration gas at the
required concentration level. Do not calibrate with expired calibration gas.
If the instrument cannot be calibrated, do not use until the reason can be determined and corrected.
Do not cover or obstruct display or visual alarm cover.
Ensure sensor inlets are unobstructed and is free of debris
The display progresses through the bUZ (Buzzer Test) Art (alarm relay test), Frt (fan relay test) then
42t (4-20 mA output test). Make sure that the settings are "on" or not disabled "diS".
During the first 10 seconds of the test cycle, the display will show bUZ and set off the audible buzzer
The alarm relay will be closed, so any devices connected to that relay will be tested.
The Fan relay will be activated for the next 1 minute of the test, so if the fan circuits are wired in the
normal manner, the fan should run.
The 4-20mA output will then ramp up from 4 to 16 mA over the next 130 seconds of the test, so if the
circuit is wired in the normal manner, the control panel or building automation system should respond.
At the end of the test cycle, the light will turn green and be on steady (Normal Operation), the fan &
alarm relay will be in standby mode and the 4-20 mA output will return to 4 mA (in clean air).
!
WARNING
19