GM40AV Series General Purpose Electromechanical Commercial Time Switches
Installation & Operating Instructions
Risk of Fire or Electric Shock
WARNING
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• More than one circuit breaker or disconnect switch may be required to de-energize the equipment before
servicing.
• Do not use the manual shut-off position of the timer for equipment servicing. Always disconnect the power
at the circuit breaker(s) or disconnect switch(es).
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• This Time Switch is designed to control one or two single phase loads. Do not use to directly control three
phase loads. Consult a qualified electrician if you are required to control three phase equipment.
• Some terminals in the Time Switch may be energized even if the yellow and green LED indicators are OFF.
• The circuit conductors shall have an ampacity not less than the maximum total load to be controlled.
• For all connections, use COPPER conductors ONLY – min. #8 AWG wires for 40 A loads, or #10 AWG wires
for 30 A loads, min. 90°C (194°F)
• Over current protection shall have an interrupting rating sufficient for the application control circuit voltage
and the total load current of the equipment being controlled.
• A fuse or circuit breaker shall be connected in series with each ungrounded conductor (and shall be able to
simultaneously open each conductor.
• Check all terminals and wires with an appropriate voltage meter before touching.
• This enclosure does not provide grounding between conduit connections. When metallic conduit is used,
you must also install grounding type bushings and jumper wire, in accordance with the (NEC) National
Electrical Code requirements.
• For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the
UL514B (standard for fitting conduit and outlet boxes) are to be used.
• Replace plastic insulator covering terminals before powering ON.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
• Jumper wires are not included.
• Alterations or modifications to the device will void warranty
Read Instructions completely before installation and retain this booklet for future reference.
INSTALLATION INSTRUCTIONS
1. Open door and remove the interior protective cover by releasing the spring latch. (See Figure 1)
2. Remove the printed circuit board by releasing the spring latch holding the bottom of the board.
(see Figure 1)
3. Select knockouts to be used. Remove the inner 1/2" knockout by inserting a flathead screwdriver
in the slot and carefully punch the knockout loose. Remove slug. If 3/4" knockout is required,
remove the outer ring with pliers after removing the 1/2" knockout. Smooth edge with knife, if
necessary.
4. Place the enclosure in the desired mounting location, and mark the three mounting holes (refer to
Figure 2 for dimensions). Install the top screw first with one of the supplied spacers, and then hang
the enclosure by the keyhole. Drive the remaining two screws at the bottom of the enclosure
through the mounting holes while passing each screw through one of the supplied spacers and in
to the wall.
5. Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs
into enclosure, carefully tighten hub lock nut. Do not over-torque.
6. Replace printed circuit board making sure to engage spring latch at the bottom of PCB.
7.
Wire in accordance with national and local electrical and safety codes (see wiring diagrams).
8. Grounding: Terminate all ground wires to the ground lug inside the case at the bottom of the
enclosure.
9. Replace interior protective cover.
10. Close the enclosure door.
PROGRAMMING INSTRUCTIONS
SETTING THE CLOCK TIME
Rotate the program dial gradually clockwise until the time of day on the outer dial is nearly aligned with
the triangle marker at the 2 o'clock position. Then set time to the minute by rotating minute hand
clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on
the inner dial.
SETTING ON/OFF TIMES
Move the white tab (tripper) on the outer dial outward at the start of the desired ON period. Move each
adjacent tab outward until the desired OFF time is reached. (See Fig. 3)
ELECTRICAL RATINGS
NO Contacts:
40 A Resistive, 120-277 VAC
30 A Ballast, 120 VAC
20 A Ballast, 277 VAC
15 A Tungsten, 120 VAC
300 VA Pilot Duty, 120-240 VAC
1 HP, 16 FLA, 90 LRA @ 120 VAC
2 HP, 12 FLA, 52 LRA @ 208-277 VAC
NC Contacts:
30 A Resistive, 120-277 VAC
10 A Ballast, 277 VAC
2 A Tungsten, 120 VAC
1 HP, 12 FLA, 30 LRA @ 120 VAC
2 HP, 10 FLA, 30 LRA @ 240 VAC
Interior
Timer Mechanism
Protective
Cover
Spring Latch
Figure 1 - PCB Latch
TRIPPERS OUT
Green Status LED: ON
(Normally-open contacts closed)
TRIPPERS IN
Green Status LED: OFF
(Normally-open contacts open)
MANUAL OVERRIDE OPERATION
With the manual switch in the middle position, the GM40AV is in
automatic mode and will switch at the programmed times.
In the upper position "I", the load is continuously ON.
Figure 3
In the lower position, "O", the load is continuously OFF.
GM40AV SERIES TERMINAL DESIGNATIONS
208/240 VAC Application One Load
T
TIMER
L 1
L 2/N
NC
NO
COM
L1
L2
120/277 VAC Application Two Loads
T
TIMER
L 1
L 2/N
NC
NO
COM
L
N
WIRING CONNECTIONS:
Screw box lug terminals
ENVIRONMENTAL RATINGS:
Operating Temperature Range:
–40° F to 131° F (–40° C to 55° C)
Operating Humidity:
10-95% RH, non-condensing
ENCLOSURE DIMENSIONS:
8.795" H x 6.631" W x 2.935" D
SHIPPING WEIGHT:
2 lbs.
6-1/8"
2-1/2"
Figure 2 - Rear View of Enclosure
with mounting hole dimensions
NC 2
NO 2
COM2
LOAD
#1
NC 2
NO 2
COM2
LOAD
LOAD
#1
#2

Publicidad

loading

Resumen de contenidos para Intermatic GM40AV Serie

  • Página 1 GM40AV Series General Purpose Electromechanical Commercial Time Switches Installation & Operating Instructions Risk of Fire or Electric Shock WARNING ELECTRICAL RATINGS NO Contacts: WIRING CONNECTIONS: • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing. 40 A Resistive, 120-277 VAC Screw box lug terminals •...
  • Página 2 Série de GM40AV Commutateurs horaires commerciaux électromécaniques d’usage universel. Directives d’installation et de Fonctionnement AVERTISSEMENT Risque d’incendie ou de choc électrique CARACTÉRISTIQUES NOMINALES CONNEXIONS DU CÂBLAGE : Contacts NO : • Débrancher l’alimentation aux disjoncteurs ou interrupteurs généraux avant l’installation ou l’entretien. Bornes à...
  • Página 3 Serie GM40AV Uso general Interruptores de tiempo electrómecanico comerciales Instrucciones de Instalación y Operación ADVERTENCIA Riesgo de incendio o descarga eléctrica CAPACIDAD ELÉCTRICA NOMINAL NO Contactos CONEXIONES DEL CABLEADO: • Desconecte la energía desde los disyuntores o los interruptores de desconexión antes de realizar la instalación o Resistencia de 40 A a 120-277 V CA Terminales de puesta a tierra en caja con el mantenimiento.
  • Página 4 LIMITED ONE-YEAR WARRANTY If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge. This warranty is extended to the original household purchaser only and is not transferable.