5. If mounting in wet environments, liquid-tight cables (Figure 6)
or flexible conduit fitting (Figure 7) are required (not supplied) to
ensure that the enclosure maintains a watertight Type 4 rating.
Install the liquid-tight cables or flexible conduit fitting into the
conduit nuts in front of the power supply and motor connectors
(Figures 6 and 7, page 8).
s
WARNING
!
conduit and fittings must be used to maintain Type 4 rating
(Figures 6 and 7). If you use water-resistant cables to run
electrical wire to the pump (Figure 6), tighten the supplied
cable/conduit connector to torque of 106 in-lbs (13 Nm).
If you use flexible conduit fittings to run electrical wire to the
pump (Figure 7), tighten the supplied cable/conduit connector
to a torque of 106 in-lbs (13 Nm), compressing the O-ring against
the outside housing of the flow control.
s
NOTICE
!
with the arrow pointing towards the flow control, as shown
in the figures.
6. Route supply wires through the flexible conduit fitting into the
wiring chamber of the flow control.
7.
Connect the supply ground wires to the ground lug in the
wiring compartment.
s
NOTICE
!
is marked at its terminal using the
8. Connect the supply wires to the screw terminal marked
L and N (Figure 5). Use only copper wires rated for at
least 60 °C. Lead wire terminals should be tightened
to a torque of 4 in-lbs (0.5 Nm).
9. Connect the motor wires to the screw terminal marked
U and V (Figure 5). Use only copper wires rated for at
least 60 °C. Lead wire terminals should be tightened
to a torque of 4 in-lbs (0.5 Nm).
10. Replace the cover and tighten the screws. For proper sealing,
the screws should be tightened to a torque of 13 in-lbs (1.5 Nm).
11. Once the cover has been replaced, ensure that the pump has
been correctly primed and reconnect the main breaker.
Liquid-tight cables or flexible
Install the cable/conduit connector
The safety earth ground connection
symbol (Figure 5).
Voltage Rating Table
On the product label, verify the voltage rating for the device and do
not exceed that voltage rating.
Supply Voltage
Motor Voltage
Single-phase 115 V
Single-phase 115 V
Single-phase 230 V Single-phase 230 V
Electrical Diagrams
115 VAC 50-60 Hz
L1
230 VAC 50-60 Hz
N/L2
115 VAC 50-60 Hz
230 VAC 50-60 Hz
Figure 5a
InlineSWC and InlineADJ
115 VAC 50-60 Hz
230 VAC 50-60 Hz
Figure 5b
InlineSWP
Electrical
Motor Power kW
Diagram
Not more than 0.75
See Figure 5
Not more than 1.5
See Figure 5
L1
N/L2
115 VAC 50-60 Hz
230 VAC 50-60 Hz
7