Quick Guide
Branch circuit protection
To protect the installation against electrical and fire
hazards, protect all branch circuits in an installation, switch
gear, machines, and so on, against short circuits and
overcurrent according to national/international regulations.
Short-circuit protection
Use the fuses mentioned in Table 1.4 to protect service
personnel or other equipment if there is an internal failure
in the unit or short circuit on DC-link. If there is a short
circuit on the motor or brake output, the frequency
converter provides full short-circuit protection.
FC 51
Bussmann
1x200–240 V
kW
Type RK1
0K18–0K37
KTN-R15
0K75
KTN-R25
1K5
KTN-R35
2K2
KTN-R50
3x200–240 V
0K25
KTN-R10
0K37
KTN-R15
0K75
KTN-R20
1K5
KTN-R25
2K2
KTN-R40
3K7
KTN-R40
3x380–480 V
0K37–0K75
KTS-R10
1K5
KTS-R15
2K2
KTS-R20
3K0
KTS-R40
4K0
KTS-R40
5K5
KTS-R40
7K5
KTS-R40
11K0
KTS-R60
15K0
KTS-R60
18K5
KTS-R60
22K0
KTS-R60
Table 1.4 Fuses
MG02BC4P
Quick Guide•Kurzanleitung•Guide rapide•Guía rápida•Guia Rápido•Краткое
руководство
Maximum fuses UL
Bussmann
Bussmann
Littelfuse
Type J
Type T
JKS-15
JJN-15
JKS-25
JJN-25
JKS-35
JJN-35
JKS-50
JJN-50
JKS-10
JJN-10
JKS-15
JJN-15
JKS-20
JJN-20
JKS-25
JJN-25
JKS-40
JJN-40
JKS-40
JJN-40
JKS-10
JJS-10
JKS-15
JJS-15
JKS-20
JJS-20
JKS-40
JJS-40
JKS-40
JJS-40
JKS-40
JJS-40
JKS-40
JJS-40
JKS-60
JJS-60
JKS-60
JJS-60
JKS-60
JJS-60
JKS-60
JJS-60
Danfoss A/S © 10/2017 All rights reserved.
Overcurrent protection
To avoid overheating of the cables in the installation,
provide overload protection. Always carry out overcurrent
protection according to national regulations. Fuses must be
designed for protection in a circuit capable of supplying a
maximum of 100000 A
(symmetrical), 480 V maximum.
rms
Non-UL compliance
If UL/cUL is not to be complied with, use the fuses
mentioned in Table 1.4, which ensure compliance with
EN50178/IEC61800-5-1:
If there is a malfunction, not following the fuse recommen-
dation may result in damage to the frequency converter
and the installation.
Ferraz
Ferraz Shawmut
Shawmut
Type RK1
Type CC
KLN-R15
ATM-R15
KLN-R25
ATM-R25
KLN-R35
–
KLN-R50
–
KLN-R10
ATM-R10
KLN-R15
ATM-R15
KLN-R20
ATM-R20
KLN-R25
ATM-R25
KLN-R40
ATM-R40
KLN-R40
–
KLS-R10
ATM-R10
KLS-R15
ATM-R15
KLS-R20
ATM-R20
KLS-R40
ATM-R40
KLS-R40
ATM-R40
KLS-R40
–
KLS-R40
–
KLS-R60
–
KLS-R60
–
KLS-R60
–
KLS-R60
–
Maximum fuses
non–UL
Type RK1
Type gG
A2K-15R
16A
A2K-25R
25A
A2K-35R
35A
A2K-50R
50A
A2K-10R
10A
A2K-15R
16A
A2K-20R
20A
A2K-25R
25A
A2K-40R
40A
A2K-40R
40A
A6K-10R
10A
A2K-15R
16A
A6K-20R
20A
A6K-40R
40A
A6K-40R
40A
A6K-40R
40A
A6K-40R
40A
A6K-60R
63A
A6K-60R
63A
A6K-60R
80A
A6K-60R
80A
11
1
1