Configuration
I n
entrées
Type de capteur,
signal et échelle de
l'entrée principale
Typ
TYPE
4 DIGITS
CAPTEUR
sans point déc.
avec point déc.
Capteur: TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S °F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
10
TC B °C
44/1800
44.0/999.9
11
TC B °F
111/3272
111.0/999.9
12
TC E °C
-100/750
-100.0/750.0
13
TC E °F
-148/1382
-148.0/999.9
14
TC N °C
0/1300
0.0/999.9
15
TC N °F
32/2372
32.0/999.9
16
TC L °C
0/600
0.0/600.0
17
TC L °F
32/1112
32.0/999.9
18
TC U °C
-200/400
-199.9/400.0
19
TC U °F
-328/752
-199.9/752.0
20
TC G °C
0/2300
0.0/999.9
21
TC G °F
32/4172
32.0/999.9
22
TC D °C
0/2300
0.0/999.9
23
TC D °F
32/4172
32.0/999.9
24
TC C °C
0/2300
0.0/999.9
25
TC C °F
32/4172
32.0/999.9
26
TC °C
personnalisé
personnalisé
27
TC °F
personnalisé
personnalisé
Capteur: RTD
28
PT100 °C
-200/600
-199.9/600.0
29
PT100 °F
-328/1112
-199.9/999.9
30 JPT100 °C
-200/600
-199.9/600.0
31 JPT100 °F
-328/1112
-199.9/999.9
Capteur: PTC - NTC
32
PTC °C
-55/120
-55.0/120.0
33
PTC °F
-67/248
-67.0/248.0
34
NTC °C
-10/70
-10.0/70.0
35
NTC °F
14/158
14.0/158.0
Capteur: Tension + Courant
36
0...60mV
-1999/9999
-199.9/999.9
37
0...60mV
linéaris. pers.
linéaris. pers.
38 12...60mV
-1999/9999
-199.9/999.9
39 12...60mV
linéaris. pers.
linéaris. pers.
40
0...20mA
-1999/9999
-199.9/999.9
41
0...20mA
linéaris. pers.
linéaris. pers.
42
4...20mA
-1999/9999
-199.9/999.9
43
4...20mA
linéaris. pers.
linéaris. pers.
44
0...10V
-1999/9999
-199.9/999.9
45
0...10V
linéaris. pers.
linéaris. pers.
46
2...10V
-1999/9999
-199.9/999.9
47
2...10V
linéaris. pers.
linéaris. pers.
48
0...5V
-1999/9999
-199.9/999.9
49
0...5V
linéaris. pers.
linéaris. pers.
50
1...5V
-1999/9999
-199.9/999.9
51
1...5V
linéaris. pers.
linéaris. pers.
52
0...1V
-1999/9999
-199.9/999.9
53
0...1V
linéaris. pers.
linéaris. pers.
54 200mV...1V
-1999/9999
-199.9/999.9
55 200mV...1V
linéaris. pers.
linéaris. pers.
Capteur: personnalisé PT100 - PTC - NTC
56
PT100
personnalisé
personnalisé
JPT
57
PTC
personnalisé
personnalisé
58
NTC
personnalisé
personnalisé
Si non disponible, les limites mini et maxi sont mises à 0.
En cas de linéarisations personnalisées, les limites pour les erreurs LO ou HI sont les
valeurs de calibration.
Si ces limites ne sont pas dépassées, elles sont prises en compte comme limites LO_S
et HI_S.
Erreur maximale
de non-linéarité pour
thermocouples (TC),
thermorésistance (PT100)
et thermistances (PTC, NTC)
L'erreur est calculée comme écart par
rapport à la valeur théorique avec
référence en % à la valeur de pleine
échelle exprimée en degrés Celsius (°C)
• Paramètres entrées TC / LIN
3 DIGIT + signe
(pour mod. 96 uniquement)
sans point déc.
avec point déc
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
non disp.
non disp.
non disp.
non disp.
-100/750
non disp.
-148/999
non disp.
0/999
non disp.
32/999
non disp.
0/600
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
0/999
non disp.
32/999
non disp.
0/999
non disp.
32/999
non disp.
0/999
non disp.
32/999
non disp.
personnalisé
personnalisé
personnalisé
personnalisé
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-55/120
-55.0/99.9
-67/248
-67.0/99.9
-10/70
-10.0/70.0
14/158
14.0/99.9
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
-999/999
-99.9/99.9
linéaris. pers.
linéaris. pers.
personnalisé
personnalisé
personnalisé
personnalisé
personnalisé
personnalisé
S, R échelle 0...1750°C; erreur < 0,2% p.e. (t > 300°) / pour d'autres échelles: erreur < 0,5% p.e.
T
erreur < 0,2% p.e. (t > -150°C)
B
échelle 44...1800°C; erreur < 0,5% p.e. (t > 300°) / échelle 44,0...999,9; erreur < 1% p.e. (t > 300°C)
U
échelle -99,9...99,9 et -99...99°C; erreur < 0,5% p.e. / pour d'autres échelles: erreur < 0,2% p.e. (t > -150°C)
G
erreur < 0,2% p.e. (t > 300°C)
D
erreur < 0,2% p.e. (t > 200°C)
C
échelle 0...2300; erreur < 0,2% p.e. / pour d'autres échelles: erreur < 0,5% p.e.
NTC erreur < 0,5% p.e.
Tc type J, K, E, N, L
erreur < 0.2% p.e.
PT100, JPT100 et PTC
erreur < 0.2% p.e.
Sélection du temps
d'acquisition (résolution).
Pour entrée linéaire
uniquement
Filtre numérique entrée
principale
Filtre numérique sur
l'affichage de la mesure
Position point décimal
pour l'échelle entrée
principale
Limite mini échelle
entrée principale
et sortie analogique
Limite maxi échelle
entrée principale
et sortie analogique
Offset de correction
entrée principale
Choix de la fonction
entrée logique
Fonction touche
«incr.» (active en
affichage P.V.)
Fonction touche
«décr.» (active en
affichage P.V.)
Limite basse réglage
seuils d'alarme
Limite haute réglage
seuils d'alarme
29
0
120ms
> 13bit; 8000 points
1
60ms
> 13bit; 8000 points
2
30ms
> 12bit; 4000 points
3
15ms
> 11bit; 2000 points
+4 filtre inhibé
(moyenne des 8 derniers échantillons)
0.0 ... 20.0 s
0.0 ... 9.9
points d'échelle
dP
Format
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
(*) non disponible pour échelles
TC, RTD, PTC, NTC
mini...maxi
échelle de l'entrée
sélectionnée en t.P
mini...maxi
échelle de l'entrée
sélectionnée en t.P
-999 ...999
points d'échelle
d. i. - t. u. - t. d.
0
Aucune fonction
1
R.À.Z.
2
Hold
3
Flash
4
Affichage crête maxi
5
Affichage crête mini
6
Affichage delta crête
7
Reset mémorisation crête
8
Reset mémorisation crête + R.À.Z.
9
Reset alarmes
10
Reset alarmes + crête
11
Reset alarmes + R.À.Z.
12
Reset al. + R.À.Z. + crête
13
État sortie OUT1
14
État sortie OUT2
15
État sortie OUT3
L.S ... H.S