1 • INSTALLATION
• Dimensions and cut-out; panel mounting
63
48
48
99
10
Panel mounting:
Fix the device with the bracket provided before making any electrical
connections.
To mount two or more devices side by side, use the cut-out dimensions
shown above.
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC
Directive 89/336/EEC with reference to the generic Standard CEI-
EN61000-6-2 (immunity in industrial environments) and EN50081-1
(emission in residential environments). BT (low voltage) conformity to
Directive 73/23/EEC as modified by Directive 93/68.
MAINTENANCE: Repairs must be done out only by trained and
specialized personnel. Cut power to the device before accessing
internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene, etc.). Use of these solvents can reduce the
mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes
defects caused by any use not conforming to these instruction.
EMC conformity has been tested with the following connections
FUNCTION
TC input probe
"PT100" input probe
Power supply cable
Relay output wires
Serial connection wire
40T 48
TEMPERATURE INDICATOR - ALARM UNIT WITH CONFIGURABLE INPUT
70
45
45
!
For correct and safe
installation, observe the
warnings contained in
this manual.
CABLE TYPE
LENGTH
USED
0,8 mm
2
compensated
5 mt
1 mm
2
3 mt
1 mm
2
1 mt
1 mm
2
3,5 mt
0,35 mm
2
3,5 mt
INSTALLATION and
OPERATION MANUAL
SOFTWARE VERSION 3.2x
code 81642C / Edition 10 - 12/04
2 • TECHNICAL SPECIFICATIONS
Accuracy
Resolution
(function of settable sample
Main input
70
TC Type
Thermocouples (ITS90)
Cold junction error
RTD Type (scale configurable
within indicated range, with or
without decimal point, ITS90)
Max. RTD line resistance
PTC Type/ NTC Type
Max. non-linearity error
°C / °F selection
Linear scale ranges
Logic input
Function of logic input
(Trip points)
masking
Relay contacyt
Logic output
Triac output
Fault settings
(option) Transmitter / Sensor
Power Supply
(option) Analog
retransmission
Power supply
(switching)
Faceplate protection
Working / Storage
temperatures
Relative humidity
Environmental conditions of use
Installation
10
(includes R77 version)
4 digit red digit height 10mm
Display
3 mechanical keys (Raise, Lower, F)
Keys
0.2% f.s. at 25°C ambient temperature,
ts =120msec
120msec, >14bit-16000 points
60msec, >14bit-16000 points (only for linear inputs)
30msec, >13bit - 8000 points (only for linear inputs)
time)
15msec, >12bit - 4000 points (only for linear inputs)
TC, RTD, PTC, NTC
60mV, 1V Ri ≥ 1MΩ, 5V, 10V, Ri ≥10KΩ
20mA, Ri = 50Ω. adjustable digital filter
J, K, R, S, T, B, E, N
(IEC 584-1, CEI EN 60584-1, 60584-2)
L GOST, U, G, D, C. Custom linearization
available on request
0,1° / °C
DIN 43760 (PT100), JPT100
20Ω
990Ω, 25°C / 1KΩ, 25°C
See tP parameter
Faceplate configurable
-1999...9999 Configurable decimal point
position, possible 32 segment linearization
24V, 5mA (Ri = 47KΩ) 1500 V isolation or
voltage-free contact
configurable to reset memory latch, hold, flash,
zero, select max./ min. peak, peak-peak value
Maximum of three configurable alarms:
Alarms
absolute, deviation, symmetrical deviation.
Adjustable hysteresis
- exclude on power-up
Alarm
- latch reset from key and/or external contact
- insert delay filter
(DON, DBI, DOF, DPO)
- set minimum intervention time
NO (NC) 5A, 250Vac / 30Vdc
24Vdc, Rout = 500Ω (10V/20mA)
limitation to 30mA
20...240Vac ±10%, 1A max. Snubberless,
inductive and resistive load I
Alarm states can be configured in probe fault
condition
24V ±10%, 50mA
15V for transmitter, max. 50mA
1,2V for potentiometer > 100Ω
10V / 20mA on max. 500Ω resolution 12 bits
(standard) 100...240Vac/dc ±10%, 50/60Hz, 8VA
(optional) 11...27Vac/dc ±10%, 50/60Hz,8VA
IP65
0...50°C / -20...70°C
20...85% Ur non-condensing
for internal use only, altitude up to 2000m
Panel mounting, extractable from front
160 g
Weight
t = 128A
S
2
2

Publicidad

Tabla de contenido
loading

Resumen de contenidos para gefran 40T 48

  • Página 1 15V for transmitter, max. 50mA Power Supply 1,2V for potentiometer > 100Ω SERVICE: GEFRAN has a service department. The warranty excludes (option) Analog 10V / 20mA on max. 500Ω resolution 12 bits defects caused by any use not conforming to these instruction.
  • Página 2 3 • DESCRIPTION OF FACEPLATE Indication of output states: OUT 1 (Alarm 1); OUT 2 (Alarm 2); OUT 3 (Alarm 3) OUT 4 (Alarm 4) PV Display: Indication of process variable Indication of ‘HI’ or ‘Lo’ out of range “Raise” and “Lower” keys: ••...
  • Página 3: Programming And Configuration

    5 • PROGRAMMING and CONFIGURATION LEVEL 1 DISPLAY Pressed for approx. 2 sec. Password Process variable Information display PA = 99 o. 1 Alarm setpoint output 1 Protection code Conf = ON o. 2 Alarm setpoint output 2 (*) Custom linearization Hysteresis parameters o.
  • Página 4 To manage PV and IN from serial line, the code to be set in S.I is 48. s. p Serial Protocol Serial interface protocol s. o CENCAL GEFRAN Virtual instrument outputs 0 ... 31 MODBUS RTU Outputs OUTW OUT4 OUT3...
  • Página 5: Output Parameters

    • TC / LIN input parameters • Output parameters 120ms > 14bits 16000 points (. I . Output settings 60ms > 14bits 16000 points Select sampling 30ms > 13bits 8000 points time (resolution). 15ms > 12bits 4000 points For linear input only. +4 to disable digital filter F.t (average 0.
  • Página 6: User Calibration

    • Protection Value Displayed Modifiable Protection parameters parameters code o.1, o.2, o.3, o.4 o.1, o.2, o.3, o.4 o.1, o.2 o.1, o.2 none +4 to disable In and Ou pages +8 to disable CF and Sr pages +16 to enable maintenance of reset latch at power-off (for linear inputs only) +32 base configuration (the following parameters will not be displayed): In: F.t, F.d, oF., L.L, H.L Ou: On [forced to no.
  • Página 7 6 • ALARMS Normal absolute alarm Symmetrical absolute alarm AL1 + [ H1 ] AL2 + H2 AL1 + H1 AL1 - [ H1 ] time time alarm 1 inverse direct alarm 2 For AL1 inverse absolute alarm (min.) with positive H1, 1 t = 1 For AL1 inverse absolute, symmetrical alarm with hysteresis H1, 1 t = 5 (*) = OFF if disabling on power-on exists For AL1 direct absolute, symmetrical alarm with hysteresis H1, 1 t = 4...
  • Página 8: Order Code

    1N4007 diode in parallel with the coil of inductive loads that operate in DC GEFRAN spa will not be held liable for any injury to persons and/or damage to property deriving from tampering, from any incorrect or erroneous use, or...
  • Página 9 40T 48 APPENDIX • SCHEDE INGRESSI / USCITE • E/A-KARTEN • FICHAS ENTRADAS/SALIDAS • INPUT/OUTPUT BOARDS • CARTES D'ENTREES/SORTIES • PLACAS DE ENTRADAS/SAÍDAS USCITA TRIAC (OUT2) TRIAC OUTPUT (OUT2) TRIAC-AUSGANG (OUT2) SORTIE TRIAC (OUT2) SALIDA TRIAC (OUT2) SAÍDA TRIAC (OUT2) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT2 nello strumento 40T48.
  • Página 10 USCITA RELÉ (OUT2) RELAY OUTPUT (OUT2) RELAISAUSGANG (OUT2) SORTIE RELAIS (OUT2) SALIDA RELÉ (OUT2) SAÍDA DE RELÉ (OUT2) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT2 nello strumento 40T48. Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac / 30Vdc. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi.
  • Página 11 USCITA RELÉ (OUT3) RELAY OUTPUT (OUT3) RELAISAUSGANG (OUT3) SORTIE RELAIS (OUT3) SALIDA RELÉ (OUT3) SAÍDA DE RELÉ (OUT3) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT3 nello strumento 40T48. Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac / 30Vdc. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi.
  • Página 12 INGRESSO DIGITALE (OUT3) DIGITAL INPUT (OUT3) DIGITALEINGANG (OUT3) ENTREE LOGIQUE(OUT3) ENTRADA DIGITAL (OUT3) ENTRADA DIGITAL (OUT3) PROFILO Questa scheda supporta la funzione di ingresso logico come alternativa ad OUT3 nello strumento 40T48. Comando da contat- to pulito o da tensione 24V. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi.
  • Página 13 USCITA LOGICA (OUT3) LOGIC OUTPUT (OUT3) LOGIKAUSGANG (OUT3) SORTIE LOGIQUE (OUT3) SALIDA LÓGICA (OUT3) SAÍDA LÓGICA (OUT3) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT3 nello strumento 40T48. Adatta a pilotare ingressi logici, applicazione tipica per interfaccia verso interruttori statici (GTS). La schedina è...
  • Página 14 USCITA LOGICA (OUT2) LOGIC OUTPUT (OUT2) LOGIKAUSGANG (OUT2) SORTIE LOGIQUE (OUT2) SALIDA LÓGICA (OUT2) SAÍDA LÓGICA (OUT2) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT2 nello strumento 40T48. Adatta a pilotare ingressi logici, applicazione tipica per interfaccia verso interruttori statici (GTS). La schedina è...
  • Página 15 USCITA ANALOGICA (OUT3) ANALOG OUTPUT (OUT3) ANALOGAUSGANG (OUT3) SORTIE ANALOGIQUE (OUT3) SALIDA ANALÓGICA (OUT3) SAÍDA ANALÓGICA (OUT3) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT3 nello strumento 40T48. Normalmente utilizzata per la ritra- smissione del valore sonda. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi.
  • Página 16 USCITA RELÉ (OUT4) RELAY OUTPUT (OUT4) RELAISAUSGANG (OUT4) SORTIE RELAIS (OUT4) SALIDA RELÉ (OUT4) SAÍDA DE RELÉ (OUT4) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT4 nello strumento 40T48. Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac / 30Vdc. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi.
  • Página 17 USCITA SERIALE (OUT4) SERIAL OUTPUT (OUT4) SERIELLER AUSGANG (OUT4) SORTIE SERIE (OUT4) SALIDA SERIE (OUT4) SAÍDA SERIAL (OUT4) PROFILO Questa scheda supporta la funzione di uscita prevista come OUT4 nello strumento 40T48. Interfaccia seriale standard RS485. La schedina è automaticamente riconosciuta dallo strumento che abilita visibilità ed impostazione dei parametri relativi. PROFILE This board supports the output function provided as OUT4 on the 40T48 instrument.

Tabla de contenido