gefran 40T 48 Manual De Uso página 13

Ocultar thumbs Ver también para 40T 48:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
Input
I n
settings
Type of probe,
signal and scale of
main input
TYPE
Type
4 DIGIT
PROBE
without dec. point with dec. point
Probe: TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S °F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
10
TC B °C
44/1800
44.0/999.9
11
TC B °F
111/3272
111.0/999.9
12
TC E °C
-100/750
-100.0/750.0
13
TC E °F
-148/1382
-148.0/999.9
14
TC N °C
0/1300
0.0/999.9
15
TC N °F
32/2372
32.0/999.9
16
TC L °C
0/600
0.0/600.0
17
TC L °F
32/1112
32.0/999.9
18
TC U °C
-200/400
-199.9/400.0
19
TC U °F
-328/752
-199.9/752.0
20
TC G °C
0/2300
0.0/999.9
21
TC G °F
32/4172
32.0/999.9
22
TC D °C
0/2300
0.0/999.9
23
TC D °F
32/4172
32.0/999.9
24
TC C °C
0/2300
0.0/999.9
25
TC C °F
32/4172
32.0/999.9
26
TC °C
Custom
27
TC °F
Custom
Probe: RTD
28
PT100 °C
-200/600
-199.9/600.0
29
PT100 °F
-328/1112
-199.9/999.9
30 JPT100 °C
-200/600
-199.9/600.0
31 JPT100 °F
-328/1112
-199.9/999.9
Probe: PTC - NTC
32
PTC °C
-55/120
-55.0/120.0
33
PTC °F
-67/248
-67.0/248.0
34
NTC °C
-10/70
-10.0/70.0
35
NTC °F
14/158
14.0/158.0
Probe: Voltage + Current
36
0...60mV
-1999/9999
-199.9/999.9
37
0...60mV
linear custom
linear custom
38 12...60mV
-1999/9999
-199.9/999.9
39 12...60mV
linear custom
linear custom
40
0...20mA
-1999/9999
-199.9/999.9
41
0...20mA
linear custom
linear custom
42
4...20mA
-1999/9999
-199.9/999.9
43
4...20mA
linear custom
linear custom
44
0...10V
-1999/9999
-199.9/999.9
45
0...10V
linear custom
linear custom
46
2...10V
-1999/9999
-199.9/999.9
47
2...10V
linear custom
linear custom
48
0...5V
-1999/9999
-199.9/999.9
49
0...5V
linear custom
linear custom
50
1...5V
-1999/9999
-199.9/999.9
51
1...5V
linear custom
linear custom
52
0...1V
-1999/9999
-199.9/999.9
53
0...1V
linear custom
linear custom
54 200mV...1V
-1999/9999
-199.9/999.9
55 200mV...1V
linear custom
linear custom
Probe: Custom PT100 - PTC - NTC
56
PT100
custom
JPT
57
PTC
custom
58
NTC
custom
In case of non-availability, maximum and minimum limits are set to 0.
In case of custom linearization, test limits for setting LO and HI errors are given by the
calibration values.
If these limits are not exceeded, they are taken into consideration as limits LO_S and
HI_S.
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as deviation from
theoretical value and is expressed as
percentage of full scale (in °C).
• TC/LIN input parameters
3 DIGIT + sign
(model 96 only)
without dec. point
with dec. point
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
not available
not available
not available
not available
-100/750
not available
-148/999
not available
0/999
not available
32/999
not available
0/600
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
0/999
not available
32/999
not available
0/999
not available
32/999
not available
0/999
not available
32/999
not available
Custom
Custom
Custom
Custom
Custom
Custom
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-55/120
-55.0/99.9
-67/248
-67.0/99.9
-10/70
-10.0/70.0
14/158
14.0/99.9
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
custom
custom
custom
custom
custom
custom
custom
custom
custom
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other range; error < 0.5% f.s.
T
error < 0.2% f.s. (t > -150°C)
B
range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range 44,0...999,9; error < 1% f.s. (t > 300°C)
U
range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other range; error < 0.2% f.s. (t > -150°C)
G
error < 0.2% f.s. (t > 300°C)
D
error < 0.2% f.s. (t > 200°C)
C
range 0...2300; error < 0.2% f.s. / for other range; error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc: J, K, E, N, L
error < 0.2% f.s.
PT100, JPT100 and PTC error < 0.2% f.s.
Select sampling time
(resolution). For linear
input only.
Digital filter
on main input
Digital filter on process
variable display
Decimal point position for
main input scale
Minimum limit of main
input scale
and analogue output
Maximum limit of main
input scale
and analogue output
Offset correction
of main input
Select function of
digital input
Raise key function
(active only in
P.V.selection)
Lower key function
(active only in
P.V.selection)
Low limit for the alarms
set point
High limit for
the alarms set point
13
0
120ms
> 13bit; 8000 divs
1
60ms
> 13bit; 8000 divs
2
30ms
> 12bit; 4000 divs
3
15ms
> 11bit; 2000 divs
+4 to disable filter (average
of the last eight values sampled)
0.0 ... 20.0 sec
0.0 ... 9.9
scale points
dP
Format
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
(*) not available for TC,
RTD, PTC and NTC scales
min...max scale
of input selected in t.P
min...max scale
of input selected in t.P
-999 ...999
scale points
d. i. - t. u. - t. d.
0
None
1
Zero
2
Hold
3
Flash
4
Max. peak display
5
Min. peak display
6
Delta peak display
7
Peak memory reset
8
Zero + peak memory reset
9
Alarms reset
10
Peak + alarms reset
11
Zero + alarms reset
12
Peak + zero + alarms reset
13
Output status OUT1
14
Output status OUT2
15
Output status OUT3
L.S ... H.S
L.S ... H.S

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

40t 96

Tabla de contenido