Register 46: Start hourly schedule period1 SUNDAY (hour: Minutes) [read/write].
0xAAAA: Hour no defined (– – : – –).
- Byte high: Hour.
The value that is sent is the value of the hour (0h to 23h, 0xAA [170dec]: No defined) In binary 16 bits.
Value by default: 0xAA[170dec] [No defined].
- Byte low: Minutes.
The value that is sent is the value of the minutes (0min to 59min, 0xAA [170dec]: No defined) In binary
16 bits.
Value by default: 0xAA[170dec] [No defined].
Register 47: End hourly schedule period1 SUNDAY (hour: Minutes) [read/write].
0xAAAA: Hour no defined (– – : – –).
- Byte high: Hour.
The value that is sent is the value of the hour (0h to 23h, 0xAA [170dec]: No defined) In binary 16 bits.
Value by default: 0xAA[170dec] [No defined].
Byte low: Minutes.
The value that is sent is the value of the minutes (0min to 59min, 0xAA [170dec]: No defined) In binary
16 bits.
Value by default: 0xAA[170dec] [No defined].
Register 48: Start hourly schedule period2 SUNDAY (hour: Minutes) [read/write].
0xAAAA: Hour no defined (– – : – –).
- Byte high: Hour.
The value that is sent is the value of the hour (0h to 23h, 0xAA [170dec]: No defined) In binary 16 bits.
Value by default: 0xAA[170dec] [No defined].
Byte low: Minutes.
The value that is sent is the value of the minutes (0min to 59min, 0xAA [170dec]: No defined) In binary
16 bits.
Value by default: 0xAA[170dec] [No defined].
Register 49: End hourly schedule period2 SUNDAY (hour: Minutes) [read/write].
0xAAAA: Hour no defined (– – : – –).
- Byte high: Hour.
The value that is sent is the value of the hour (0h to 23h, 0xAA [170dec]: No defined) In binary 16 bits.
Value by default: 0xAA[170dec] [No defined].
- Byte low: Minutes.
The value that is sent is the value of the minutes (0min to 59min, 0xAA [170dec]: No defined) In binary
16 bits.
Value by default: 0xAA[170dec] [No defined].
Note [EEPROM]: The values of the read / write Registers are stored in EEPROM each time they are written to.
Registers only read.
Register 50: CO2 [only read].
The value that is sent is the CO2 measurement value (0ppm to 2000ppm) In binary 16 bits.
Analogic proportional Output 0...10V: Output "Measure CO2".
Measurement range: 0ppm [0x0000] to 2000ppm [0x07D0]. Another low range requested.
CO2 sensor integrated in the regulator.
46