DIP switch setting (bank S2)
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
The setting ON – ON – ON is invalid (operating
state "Fault").
AMTRON® Compact 2.0 11
The maximum charging current can be set to 6 A,
10 A, 13 A or 16 A.
DIP switch setting (bank S2)
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
The setting ON – ON – ON is invalid (operating
state "Fault").
6.1.3 Set unbalanced load limitation
The tasks described in this section may only
be carried out by a qualified electrician.
Unbalanced load refers to the uneven loading of
the phases of a three-phase alternating current net-
work. An unbalanced load must be avoided if the
vehicle is charged with one or two phases. In Ger-
many, for example, an unbalanced load exists if the
18
Max. char-
ging cur-
3
rent [A]
OFF
32
OFF
25
OFF
20
OFF
16
ON
13
ON
10
ON
6
Max. char-
ging cur-
3
rent [A]
OFF
16
OFF
16
OFF
16
OFF
16
ON
13
ON
10
ON
6
difference between two phases at the mains con-
nection point is greater than 20 A (in accordance
with VDE-N-AR-4100).
u Observe applicable national regulations.
u Set DIP switch 2 on bank S1 to "ON".
ð The unbalanced load is limited to 20 A (default
setting).
To limit the unbalanced load to a different current
value, the configuration tool is required.
1 "6.5 Description of the configuration tool"
[} 20]
6.2
Use cases
6.2.1 Downgrade
The tasks described in this section may only
be carried out by a qualified electrician.
By using the downgrade input, it is possible to re-
duce the grid connection charging current that is
not available at its maximum level under certain cir-
cumstances or at certain times. For example, the
downgrade input can be controlled by the following
criteria or control systems:
n Electricity rate
n Clock position
n Load shedding
n Manual control
n External load management
Switching contact
status
open
closed
Downgrade status
Downgrade active
Downgrade inactive