Parameter Lists; Configuration Parameters List; 5�1�1 Scroll And Modify Mode; 5�1�2 Table Of Parameters - Daikin FWTOUCH Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

5

PARAMETER LISTS

5.1 CONFIGURATION PARAMETERS LIST

5.1.1 Scroll and modify mode
Ū to scroll the list, press the OK button at the
top right;
Ū when changing the parameter, the NOT
saved value appears orange;
Ū to save the settings, press the OK button at
the top right and the text changes from or-
ange to white.
5.1.2 Table of parameters
ID
Description
C1
Unit type
C2
Pipes numbers
C3
Air probe
T e m p e r a t u r e
C4
display
C5
Ventilation type
C6
Valve type
Summer/Winter
C7
switching
Configuration out-
C8
put O7
C9
Output logic O7
C10 Heating elements
C11 Water
probe
present
C12 Number of 4-pipe
unit water probes
C13 Humidity probe
C14 ECONOMY
from
contact
C15 ON/OFF
from
contact
C16 Dehumidification
from contact
8
FWTOUCH
Default
Possible value
3 speed
3 speed
4 speed
2 pipes
2 pipes
4 pipes
Display
Display
Board
Celsius
Celsius
Fahrenheit
Step
Step
Modulating
Not included
Not included
On/Off
Modulating
From keypad/serial
From digital input
Auto on water
From keypad/serial
temperature
Auto
on
temperature
(see
dedicated
No use
paragraph)
N.A
N.A
N.C
No
No/Yes
No
No/Yes
1
1/2
Display
Display/Board
No
No/Yes
No
No/Yes
No
No/Yes
ID
Description
C17 Fan
mode
in
STANDBY
C18 Fan
speed
in
STANDBY
C19 Natural convection No
C20 Status with discon-
nected serial
C21 Language
C22 Display Stand-by
5.1.3 Configuration constraints
The configuration of the hydronic indoor unit
must take the following requirements into
account:
Ū if the heating element is present, the water
probe must also be present;
Ū if the heating element and also the valve are
present, the latter must be a 3-WAY valve
(NOT A 2-WAY VALVE);
Ū If the SUMMER/WINTER switchover is set to
"Auto on water temp.", the water probe must
air
also be present;
Ū the heating element cannot be present in the
4-pipe units;
Ū in 4-pipe units with only one water probe, it
is not possible to set summer/winter switcho-
ver to "Auto on water temp.";
Ū summer/winter switchover can be set to "Au-
to on air temp." only if the heating element is
present or if the hydronic indoor unit has a
4-pipe configuration;
Ū If the SUMMER/WINTER switchover is set to
"Auto on water temp.", a 2-way valve cannot
be used. The water probe must be installed
at a point in the hydraulic circuit with low cir-
culation.
Default
Possible value
Always ON,
Always OFF,
Standard
Cyclical switching
on
Minimum
Minimum
Medium
Maximum
No/Yes
Keypad / serial
Keypad / serial
From supervisor
Italian,
English,
Italian
French,
German,
Spanish
OFF
OFF
Clock,
Temperature

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido