SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
Battery
Red
White
Battery Connector
Important:
The SLC 5/03, 5/04, and 5/05 processors have a capacitor that
provides at least 30 minutes of battery back-up while the battery is
disconnected. Data in RAM is not lost if the battery is replaced within
30 minutes
4. Remove the battery from the retaining clips.
5. Insert a new battery into the battery retaining clips.
6. Plug the battery connector into the socket as shown above.
7. Re-insert the module into the SLC 500 chassis.
8. Restore power to the SLC 500 power supply.
9. Close the processor door.
Important:
See page 13 for information on proper battery handling, storage, and
transporting.
Publication 1747-IN009A-ML-P
Left Side View