Air damper adjustment
After loosening the screw 3, operating the screw 1, the combustion air is adjusted ac-
cording to the indications of the pointer 2. After adjustment, lock the screw 3.
Position of electrodes - baffle
After fitting the nozzle, check correct positioning of the electrodes and baffle, according
to the dimensions given below. It is advisable to check the dimensions after each oper-
ation on the head.
2÷3
2÷3
fig. 32- Position of electrodes - baffle
4.2 Commissioning
B
Checks to be made at first lighting, and after all maintenance operations involv-
ing disconnection from the systems or an operation on safety devices or parts
of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the fuel system.
Check the pre-filling of the expansion tank
Fill the water system and make sure that all air contained in the boiler and the sys-
tem has been vented by opening the air vent valve on the boiler and any vent valves
on the system.
Make sure there are no water leaks in the system, hot water circuits, connections or
boiler.
Make sure the electrical system is properly connected and the earth system works
properly.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler.
Fit the pressure gauge and the vacuum gauge on the pump (remove after starting)
of the burner.
open the gate valves along the diesel pipe
40
EN
2
3
MAX
4
AIR
2
ARIA
M
STOP
AIR
A
4
1
MIN
X
AIR
2
LUFT
STOP
AIRE
1
M
N
I
fig. 31
3
cod. 3541Q460 - Rev. 00 - 10/2015
ATLAS D ECO COND UNIT
Start-up
1
ARIA
AIR
LUFT
AIRE
A
When the thermostatic line closes, the burner motor starts turning together with the
pump: all the oil sucked is sent to the return. The burner blower and the ignition trans-
former are also working, therefore the following stages are carried out:
firebox preventilation.
prewash of a part of the oil circuit.
preignition, with discharge between electrode tips.
B
6÷6,5
At the end of prewash, the unit opens the electromagnetic valve: the oil reaches the noz-
zle, where it is finely sprayed.
Its contact with the discharge between the electrode tips creates the flame.
The safety time begins simultaneously.
Unit cycle
R-SB-W Thermostats/Pressure switches
OIl pre-heater
OH
Operation enabling contact
OW
Burner motor
M
Ignition transformer
Z
Electromagnetic valve
BV
Photoresistance
FR
Starting with pre-heater
A'
Starting without pre-heater
A
Flame present
B
Normal operation
C
Adjustment stop (TA-TC)
D
Pre-ventilation time
t1
Safety time
TSA
Pre-ignition time
t3
Post-ignition time
t3n
Pre-heating time
tw
Output signals from the unit
Necessary input signals
Checks during operation
Ignite the appliance as described in sec. 2.3.
Check that the fuel circuit and water systems are airtight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check that the water is circulating properly between the boiler and the systems.
Check the proper ignition of the boiler by performing various tests, turning it on and
off with the room thermostat or remote control.
Check that the burner door and fume chamber are tight.
Check that the burner works properly.
Analyse the combustion (with the boiler unit stable) and check that the content of
in the fumes is between 11% and 12%.
CO
2
Check the parameters are programmed correctly and perform any required custom-
ization (compensation curve, power, temperatures, etc.).
VE
P
VE
P
fig. 33 - Starting
t3n
tw
t1
t3
TSA
fig. 34 - Unit cycle