Installation Guide
Alarm Module T941AM8
9a. Connecting Alarm Inputs for Voltage-Free
Make/Break
1. Connect twisted-pairs to alarm inputs that are to
be used: J07 for inputs 1–4 and J08 for 5–8.
2. Connect supply voltage to J09.
This can be taken from J03-3 and -4.
However, for galvanic isolation an external power
supply must be connected to J09 (always used in
CTS 900).
Alarm input 1
Alarm input 2
Alarm input 3
Alarm input 4
Alarm input 5
Alarm input 6
Alarm input 7
Alarm input 8
Supply voltage
3. Check that jumpers S06–S13 are inserted for the
corresponding alarm inputs (1–8) that are used
(see dwg below).
• For voltage-free make/break of an alarm
input with common external power supply
both left and right jumper must be inserted
(i.e. in position 1-2 and 3-4).
• For voltage-free make/break of an alarm
input with individual external power supply
(e.g. nurse call) the corresponding jumper
must be in position 2-3.
• Alarm detection requires a current of at
least 0,4 mA.
• Max voltage on make/break alarm inputs
is 48 V.
4
J07
1
ALARM INPUT 1
2
3
ALARM INPUT 2
4
5
ALARM INPUT 3
6
7
ALARM INPUT 4
8
J08
1
ALARM INPUT 5
2
3
ALARM INPUT 6
4
5
ALARM INPUT 7
6
7
ALARM INPUT 8
8
J09
1 EXTERNAL 12VDC +
2 EXTERNAL 12VDC –
left jumper
1
2 3 4
S13
S12
S11
S10
S09
S08
S07
S06
Jumpers S06-S13:
S08-S13 with jumpers inserted for voltage-free
make/break with common power supply.
S07 with jumper inserted for voltage-free make/
break with individual external power supply.
S06 with jumpers removed for ring signals.
9b. Connecting Alarm Inputs for Ring Signals
1. Connect twisted-pairs to alarm inputs that are to
be used: J07 for inputs 1–4 and J08 for 5–8.
2. Check that jumpers S06–S13 are not inserted for
the corresponding alarm inputs (1–8) that are
used (see dwg. above).
• For an alarm input used for ring signals both
left and right jumpers must be removed.
10. Acknowledgement Input Connection
(Not used in CTS 900.)
1. Connect twisted-pair to ACKN, screw 1 and 2 on
connector J05, (unpolarized).
2. Connect supply voltage to J09. (See dwg at left
above). This can be taken from J03-3 and -4.
However, for galvanic isolation an external power
supply must be connected to J09.
Acknowledge input
Handook page
47/128
TD 90858GB
right jumper
J05
1
ACKN.
2
3
TEST
ACKN.
4
1995 08 31