7.13 Configuring a filter
The filter determines which data are to be displayed.
An existing filter can be edited or a new filter can be created.
In order to create a new filter, proceed as follows:
1. In the Data main menu, select the Filters submenu.
2. Click the symbol
and select a filter number for the filter slot in the drop-
down menu.
3. Click Add.
4. In the General menu, enter the desired filter name in the Name field.
5. In the Preferred units menu, select the desired units for the display.
6. In the Fields menu, select the data for the display.
In order to enable public access to the filter, activate the menu item Public access
in the General menu.
In order to display the filter created in the Data submenu, activate the menu item
Show in menu bar.
Î Click Save configuration.
In order to edit an existing filter, proceed as follows:
1. In the Data main menu, select the Filters submenu.
2. Select the desired filter and click the symbol
A view of the data filter appears.
3. Edit the filter as described before.
4. Click Save configuration.

7.14 Exporting data

In order to copy logged data onto a computer, proceed as follows:
1. In the Data main menu , select the Download submenu.
2. In the File format dropdown menu, click the desired format.
For the download, further adjustments such as file format, filter, sieve interval, time
zone, range of data to be downloaded and language can be made.
3. Click Start download.
4. Save the file in a folder of choice.
34

7.15 Erasing data

In order to erase logged data, proceed as follows:
1. In the Data main menu, select the Erase submenu.
2. In order to erase all logged data, confirm the erase notification by clicking

7.16 Setting up Modbus / BACnet

The controller connected to the terminals 1 and 2 can be connected to a build-
ing management system. For this purpose, the device offers Modbus or BACnet
functionality.
7.16.1 Setting up Modbus communication
To enable the communication over Modbus / TCP in the local network, some ad-
justments have to be made in the Modbus menu.
In order to setup the Modbus communication, proceed as follows:
1. In the Configuration main menu, select the Modbus submenu.
.
2. Activate the Modbus functionality.
The current configuration is shown under Installed configuration.
Î In order to upload a configuration, click on Select and select the desired con-
If a matching configuration has been uploaded but not yet installed, it will be indi-
cated under Matching built-in configuration.
Î In order to install a matching built-in configuration, click Apply.
Information about built-in and installed configurations can be downloaded as a
PDF file.
Î In order to download a PDF file containing data points made available, click
Erase all.
Note
The Modbus functionality will only be available, if the BACnet functionality
is deactivated.
figuration.