4. Inverter Control
4.1 Command Data (Readable and Writable)
Register No.
2500H
2501H
2502H
2503~251FH
Note 1 : Write in zero for Not used BIT, do not write in data for the reserved register.
Note 2: Bit 2 of 2501H is not for fault indication. EFO is for "external abnormity.
"External abnormity" is any event not related to drive operation which can be defined externally by the
user/machine.
When there is external abnormity, user may change the bit value from 0 to 1 through communication,
inverter will stop according to the setting in 07-09 (decel. to stop or coast to stop).
4.2 Monitor Data (Only for reading)
Register No.
2520H
Bit
Content
Reserved
Operation Signal
0
Operation Command
1
Reverse Command
2
Abnormal
3
Fault Reset
4
Jog Forward Command
5
Jog Reverse Command
6
Multi-function CommandS1
7
Multi-function CommandS2
8
Multi-function CommandS3
9
Multi-function CommandS4
A
Multi-function CommandS5
B
Reserved
C
Relay R1
D
Reserved
E~F
Reserved
Frequency Command
Reserved
Bit
0
Operation state
1
Direction state
2
Inverter operation prepare state 1:ready 0 : unready
3
Abnormal
4
DATA setting error
5-F
Reserved
1 : Run
1 :Reverse
1 : EFO (Note)
1 : Reset
1 : Jog Forward
1 : Jog Reverse
1 :"ON"
1 :"ON"
1 :"ON"
1 :"ON"
1 :"ON"
1 :"ON"
0:"OFF"
Content
1 : Run
1 : Reverse
1 : Abnormal
1 : Error
App 3-5
0 : Stop
0 :Forward
0:"OFF"
0:"OFF"
0:"OFF"
0:"OFF"
0:"OFF"
0 : Stop
0 : Forward