3.3 - Requirements for
the installation site

3.4 - Minimum distances

30
• Do not install the product immediately below a wall
outlet.
• Do not install the product in rooms with excessive humidity.
• Do not install the product outside enclosed spaces or
in areas where it could be exposed to water or moisture, e.g.
swimming pool.
• Do not install the product or its connection socket with cables
in the protection zone 1 and 2 of wet areas.
• Do not install the product in rooms whose occupants
can not vacate them independently, unless constant
supervision can be ensured.
• Note that the room temperature should be at least 17°C and keep the
fl oor areas and heaters clean in order to avoid any fogging
eff ect.
A
A = 200 mm
B = 400 mm
• Make sure you do not fall below the minimum distance (C) between the
rear wall and ceiling/wall predetermined by the fi xing brackets
(V brackets).
• Ensure that continuous air circulation is possible between the rear wall
and the ceiling/wall.
• Keep a minimum distance of 600 mm
in all directions in areas of IP classes 65/67.
B
A
C = 30 mm
C