Descargar Imprimir esta página

Pre-Installation - DURAVIT SensoWash i Lite Instrucciones De Montaje

Inodoro con lavado integrado
Ocultar thumbs Ver también para SensoWash i Lite:

Publicidad

Idiomas disponibles

Idiomas disponibles

Rated voltage
Rated power
Circuit breaker
RCD
Position of electrical connection
m m
1 4 4
"
5 ¾

Pre-installation

DANGER
Risk of fatal electric shock
> Disconnect electrical components from the power
supply before the installation.
> Check that all components are de-energised.
> Prevent the power supply from being switched on
accidentally.
> Ensure that there is no damage to the power supply
cable.
> Lay a permanent power supply line which must be
on a separate circuit.
> Observe the position of the electrical connection.
> Leave at least 500 mm (19⅝ ") of feed cable
exposed.
> Confirm that the grounding wire is 10 mm (⅜ ")
longer than the L and N wire.
> Install circuit breaker
> The product itself does not have electrical leakage
protection function, it must be installed in circuit
where there is leakage protection device installed.
> Means for disconnection must be incorporated
in the fixed wiring in accordance with the wiring
rules and having a contact separation in all poles
that provide full disconnection under overvoltage
category III conditions.
6
57307_Mounting_SensoWash i_Lite_US/19.07.1
120 V 60 Hz
1080 W
I
= min. 15 A
N
I
= 30 mA
N
Protection degree
Protection class
Cable specification
2
Positioning the mounting template
> Position the mounting template.
> Check the position and the length of the power
supply cable. The power supply cable must be at
least 500 mm (19⅝ ") long.
42
Connecting the cable
> Remove the insulation from the wires
approximately 10 to 11 mm (⅜ ").
> Connect the 3 wires to the terminal block.
Observe the L, N and PE conductors.
IP X4
I
Cross section
1 – 2.5 mm2
(17 – 14 AWG)

Publicidad

loading

Este manual también es adecuado para:

620000 01 1 40 1310