12 .10 .1 Place the main switch in the "OFF" position and wait until all the fans have stopped rotating. Lower the drain pan (see
Chap . 8) .
12 .10 .2 Use compressed air at a maximum pressure of 10 bar and at a minimum distance of 150 mm, directed perpendicularly
against the finned pack to avoid bending or damage to the fins.
12 .10 .3 Use a jet of water at a max pressure of 50 bar for damp dirt or grease at a minimum distance of 150 mm, directed
perpendicularly against the finned pack, avoiding bends or damage to the fins and pipes. If appropriate add a neutral
detergent (refer to its instructions for use). Rinse and then dry with compressed air as indicated at point 12 .10 .2 . Make
sure that the electrical components are not affected by the jet of water. If necessary, provide adequate coverage.
12 .10 .4 Aspirate possibly from the air inlet side .
12 .10 .5 After having cleaned the finned pack, perform a visual inspection to identify any dirt or the presence of fins that are
damaged (repeat the cleaning operation if necessary).
12 .11 Only use original spare parts . Do not wait until the component is completely worn out, preventive replacements can
greatly improve performance and extend the life of the model .
12 .12 For maintenance of any accessories or components mounted on the model, refer to their user-manuals.
12 .13 When replacing electric heaters take particular care during installation in order to avoid damage to the vulcanization;
correctly reset wiring and existing fastening systems to avoid possible movement during operation .
12 .14 After every maintenance work, carry out the checks before commissioning according to Chapter 10 and after commissioning
according to Chapter 11 .
12 .15 Always take into account the working pressure of the system: in the event of a rupture, there is a risk of injury to persons
or damage to property due to the projection of debris, even from a great distance. Before carrying out any work, always
make the system safe as per current regulations. The use of PPE is recommended (see Chapter 13) .
12 .16 In the event of a leak of refrigerant fluid, check that it has not penetrated into rooms below or adjacent to the place of
installation: secure the rooms as per current regulations.
12 .17 Do not use the ventilation ducts to evacuate refrigerant vapours .
12 .18 In the event of fire, evacuate the premises immediately and take all safety measures in accordance with the regulations
in force .
12 .19 When dismantling and scrapping the unit, ensure that the appropriate PPE is used (see Chapter 13) .
Ensure that the fluids are completely drained and properly disposed of. Pay particular attention to sharp edges.
Figure 5
33
www.modine.com