VLT® Soft Starter MCD 600
Model
Nominal rating [A]
MCD6-0527B
550
MCD6-0579B
580
Table 7: MCD6-0020B~MCD6-0579B, 600 V AC
Model
Nominal rating (A)
350%, 30 s
MCD6-0020B
18
MCD6-0034B
30
MCD6-0042B
38
MCD6-0063B
52
MCD6-0069B
64
MCD6-0086B
70
MCD6-0108B
88
MCD6-0129B
105
MCD6-0144B
120
MCD6-0171B
144
MCD6-0194B
164
MCD6-0244B
212
MCD6-0287B
247
MCD6-0323B
279
MCD6-0410B
404
MCD6-0527B
449
MCD6-0579B
495
Adjust the continuous current setting of the circuit breaker to match the specified rating.
1
40 | Danfoss A/S ©
@480 V AC
Fault current 65 kA
Fuse rating [A]
Fuse class
600
600
@600 V AC
Fault current 50 kA
Circuit breaker, (rating, A)
UTS150LxxU-040 (40 A)
UTS150LxxU-060 (60 A)
UTS150LxxU-070 (70 A)
UTS150LxxU-100 (100 A)
UTS150LxxU-125 (125 A)
UTS150LxxU-150 (150 A)
UTS150LxxU-150 (150 A)
UTS250LxxU-250 (250 A)
UTS400LxxU-300 (300 A)
UTS400LxxU-350 (350 A)
UTS400LxxU-400 (400 A)
UTS800L-NGx-600 (600 A)
UTS800L-NGx-800 (800 A)
UTS1200P-NGx-1000 (900 A
(1)
UTS1200P-NGx-1000 (1000 A)
UTS1200P-NGx-1200 (1200 A)
UTS1200P-NGx-1200 (1200 A)
Circuit breaker rating [A]
HND63B100 (1000)
HLD3600 (600)
SGLA36AT0600 (600)
UTS800H-NGx-800 (800)
HND63B120 (1200)
HLD3600 (600)
SGLA36AT0600 (600)
UTS800H-NGx-800 (800)
HND63B120 (1200)
Fault current 100 kA
Fuse rating, (A, max)
40
60
70
100
125
200
250
300
300
350
400
500
700
)
700
800
900
1000
AN43852230046601-000101 / 175R1190
Fuse class
Any (J, T, K-1, RK1, RK5)
Any (J, T, K-1, RK1, RK5)
L