Reconfiguring the solenoid valve controller
By default, the solenoid valve controller is set so that at the start of hygiene flushing
both solenoid valve cartridges are opened.
10.9 Press the TEST key.
• The LED flashes 4 × briefly.
• The fitting goes into Hygiene Mode.
• The LED flashes at 1 second intervals.
10.10 Press the
• The LED in the sensor flashes.
– Short = only the solenoid valve cartridge for cold water opens.
– Long = both solenoid valve cartridges open.
Exiting from Hygiene Mode
After a hygiene flushing cycle has completed, the fitting automatically switches to
Normal Mode.
10.11 Press the TEST key.
• The LED in the sensor flashes 4 × briefly.
or
Wait 60 seconds.
• The LED in the sensor does not flash.
TD Mode
Starting thermal disinfection
Warning!
Protective measures for persons (scald-protection) must be provided during thermal
disinfection, e.g. closing off sanitary rooms.
Failure to observe can cause bodily harm due to scalding.
10.12 Press and hold the RESET key.
10.13 Additionally press the
• The LED flashes 4 × briefly.
• The fitting switches to Normal Mode.
• The LED flashes twice with a 1s interval.
10.14 Press the ON key.
• The LED flashes with 2s intervals.
• Thermal disinfection is started.
OFF key.
OFF key within 2s.
13