Hazard information
During installation, make sure that both DALI and mains voltage-car-
rying lines are disconnected. If one or more circuit breakers supply
hazardous voltages, they must be labelled with a warning or option-
ally coupled.
The type, cross-section and routing of the control cable used must
be in accordance with the regulations for 230 V cables. DALI and
mains voltage wires can be routed in a cable (e.g. 5 x 1.5 mm²).
For secure operation, the device must be installed in a power distribu-
tion panel according to VDE 0603, DIN 43871 (low-voltage sub-distri-
bution board), DIN 18015-x. The installation must be on a mounting
rail (DIN rail) according to EN 60715. Installation and wiring must be
performed according to VDE 0100 (VDE 0100-410, VDE 0100-510
etc.). Please consider the technical connection requirements (TAB) of
your energy supplier.
Disconnect and cover nearby live parts before installing and con-
necting the device.
The device may only be operated within a domestic environment, in
business and trade areas and in small enterprises.
If you use the device/system in a security application, it must be op-
erated in conjunction with a UPS (uninterruptible power supply) in
order to bridge possible power failure.
Using the device for any purpose other than that described in this
operating manual does not fall within the scope of intended use and
will invalidate any warranty or liability.
DALI emergency lighting systems are not supported.