Descargar Imprimir esta página

Emerson Digistart CS Guia Del Usuario página 9

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
5.
Troubleshooting
Table 5-1 General faults
Display Indication
No display
AMPS or TEMP
LED flashing
Four dashes on display and
RS485 LED flashing
-
-
6.
Specifications
Enclosure
Front Panel Height ............................................................................................................................................................... 120 mm
Front Panel Width ................................................................................................................................................................ 120 mm
Inside Panel Depth (when mounted) .............................................................................................................................. 30 mm (max)
Panel Cutout ............................................................................................................................................................................ 92 mm
Weight ....................................................................................................................................................................................... 450 g
Power Suply
Voltage ..................................................................................................................................................... 18 - 30 Vdc/Vac (50/60 Hz)
Consumption ........................................................................................................................................ 100 mA (max - steady state)
Connection (Terminals 1, 2) ................................................................................................. 2 pole spring clamp connector terminals
RS485 serial network port (optional)
RS485 Network Interface .......................................................................................... AP ASCII or Modbus RTU protocol (selectable)
Connection (Terminals B6, B7, B8) ...................................................................................... 3 pole spring clamp connector terminals
RS485 serial starter port (soft starter connection)
RS485 Soft Starter Interface ............................................................................................................... AP ASCII protocol as standard
Connection (Terminals B1, B2, B3) ...................................................................................... 3 pole spring clamp connector terminals
Analog output
Motor Current Monitoring Interface ....................................................................................................... 4-20 mA (max burden 200
Connection (Terminals B10, B11) ......................................................................................... 2 pole spring clamp connector terminals
Sundry
Enclosure Rating ..................................................................................................... IP54 or NEMA 12 when correctly panel mounted
Pollution Degree .................................................................................................................................................. Pollution Degree 3
Operating Temperature .............................................................................................................................................. - 5
Relative Humidity ............................................................................................................................ 5 to 95% (max non-condensing)
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in
which case the user may be required to employ additional mitigation methods.
Approvals
CE
............................................................................................................................................................................ IEC 60947-4-2
UL and C-UL .......................................................................................................................................................................... UL 508
C
............................................................................................................................................................................ IEC 60947-4-2
Remote Keypad User Guide
Issue 1
Problem
No control voltage
Soft starter in restart delay mode
The Remote Keypad has detected a
loss of communication on the RS485
link to the soft starter
Incorrect or no 4-20 mA analog output
signal
The motor cannot be started
www.controltechniques.com
Possible Solution
Check that correct voltage is present at terminals 1, 2.
Wait for the restart delay (programmed in the soft starter)
to elapse.
Verify and solve the cause for loss of communication.
If communication is restored before the soft starter trips,
the display will return to active status and the RS485 LED
will illuminate. If communication is restored after the soft
starter has tripped, the display will indicate the trip code.
Use the Reset button to reset the soft starter fault.
Check the correct voltage is present at terminals 1, 2.
Check that correct polarity is used at terminals B10, B11.
Check that the Motor FLC, Analog Output 4 mA Offset and
Current ÷ 10 parameters are set correctly.
Check that control voltage is connected to the starter.
If connected to a Digistart CS, check that terminals
CSL-DI2 on the starter are linked.
Pr 8 on the Remote Keypad must be set to 0 or 1.
2
Ω
)
o
o
C / + 60
C
9

Publicidad

loading