E) CONTROLLING THE THERMOSTAT
Description of buttons and control lights:
Turn the device on or off.
SET Used to enter the programming and set the requisite value.
Display the entered value in the display mode.
In the programmable menu, it is used to move through the list of functions and to increase the requisite
value. Display the set differential in the display mode.
In the programmable menu, it is used to move through the list of functions and to decrease the requisite
value.
Kontrolky:
WORK: lit = contact switched on
not lit = contact switched off
SET:
lit = user setting or programmable menu setting is in progress.
Display mode
Displays the current sensor temperature. Use the
indicator lights.
Mode for setting the requisite value
To enter, hold down the SET button for more than 3 seconds. In this state, the SET indicator lights up.
Use the arrows to set the new value. The newly set value can be saved by pressing the SET button again
for 3 s or it is saved automatically after 20 s.
Programmable menu mode
To enter the menu, press and hold the SET button for 3 s. Use the arrows to select the function you want to
change (1 - 6). Confirm with the SET button. Use the arrows to set the new value. Press the SET button for 3
seconds to save the new value and return to programming mode. Using the SET button again for 3 seconds
will save the set parameters and return to the display mode.
Description of display states:
- Display mode: Default display. Displays the current sensor temperature.
- Mode for setting the requisite value: Used to set the on/off value.
- Programmable menu mode: Used to select the requisite function and its setting.
TABLE 17) TECHNICAL PARAMETERS OF THERMOSTAT
Temperature range
Power voltage
Energy consumption
Switching differential
Max. upper ambient temperature
Thermostat delay
Accuracy
Instalation locations
Contact load
TABLE 18) SETTABLE OPTIONS FOR THE THERMOSTAT
Symbol
F1
Switching differential
F2
Thermostat delay
F3
Min. requisite values
F4
Max. requisite values
F5
Function
F6
Temperature correction
• info@thermis.cz • www.thermis.cz •
Function
1.cooling, 2.heating, 3.alarm
• (+420) 545 226 177-184 •
buttons, see the description of the buttons and
normal enviroment
Adjustable range
1°C - 16°C
0 - 9 min
-50°C - req. temp.
req. temp. -99°C
-5°C - 5°C
• Thermis, spol. s r.o. • Mateří 14 •
• 614 00 Brno • Czech Republic •
0°C - 99°C
230V
max. 5W
1°C - 16°C
60°C
0 - 9 min
1°C
10A/250V
Factory settings
2°C
0 min
0°C
99°C
2
0°C
EN