OWNER/INSTALLATION MANUAL
3�0 INSTALLATION
Installation must only be attempted by competent
personnel�
3�1 POSITIONING AND AIRFLOW
The heat pump must be positioned in a well
ventilated area. Minimum distances between the heat
pump and any obstructions are shown below.
• The heat pump must be fixed by M10 bolts to a
concrete base or mounting brackets. These must be
Important installation instruction
solid and fixed securely. Brackets must be corrosion
proof.
• Do not block inlet or outlet grilles.
10
500mm
500mm
Airflow - general principles
The heat pump absorbs energy from the air drawn
through it. To function effectively the heat pump must
have access to the fresh air it needs.
• Air must not recirculate. The air leaving the heat
pump must not be sucked back into the inlet.
• Air must not be restricted. The air volume must not
be reduced.
• The minimum required distances shown below
must be provided to minimise the risk of air
recirculation or restriction and reduction in
performance. Further examples are shown on the
following page.
3000mm
500mm
1005759 ISSUE 5