AERMEC BMS pCO5 Manual De Instrucciones página 13

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Digital variables
r= Command code Modbus =1
r/W = Command code Modbus = 5
Modbus address
1
Unit On/Off
2
Summer/Winter request from Supervisor
3
Alarms reset (1= reset)
4
System switch-on request from digital input
5
System cold/hot request from digital input (closed=Cold)
6
Recovery switch-on request from digital input
7
8
9
Recovery On/Off from Superv.
10
System On/Off from Superv.
11
12
Cold regulation on fixed set (0) or climatic curve (1)
13
Winter regulation on fixed set (0) or climatic curve (1)
14
Recovery regulation on fixed set (0) or climatic curve (1)
15
Enables system pump
16
Enables recovery pump
17
18
On/Off General System
21
Enab. Recovery differential auto calculation
22
23
24
25
26
27
28
Active recovery low load function
29
Active system low load function
30
Evaporator pump 1
31
Evaporator pump 2
34
Recovery pump 1
35
Recovery pump 2
36
CCP1 - Circ.1 compressor 1
37
CP1A - Circ.1 compressor 2
38
CCP1B - Circ.1 compressor 3
39
CCP2 - Circ.2 compressor 1
40
CCP2A - Circ.2 compressor 1
41
CCP2B - Circ.2 compressor 3
42
CV - Fan 1
43
CV1 - Fan 2
44
VIC- cycle inversion valve, Circ 1
45
VIC- cycle inversion valve, Circ 2
46
VS2 - circ.1 liquid solenoid valve 1
47
VS2 - circ.2 liquid solenoid valve 1
48
Description
r/W
R
R/W
R/W
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
BMS - pCO5 1309 5806600_00
13