Calibration menu
Alarm history menu
Info menu
Hold down the reset
button to confirm the selection.
To exit the "SERVICE MENU" press the reset button until the word "MENU" flashes, release the button: the display shows last submenu
selected. Press reset button until the word "MENU" flashes, release the button: the display shows the set point temperature.
Parameters menu
The index of the first parameter will appear followed by the value set upon menu activation
Turning the knob the subsequent parameters will be displayed
Once the parameter to be changed has been identified press the reset button. The editable value will appear flashing and by turning the knob it
will be possible to make the change
To store the value press the reset button.
Exit from the menu automatically stops after 5 minutes of inactivity or by pressing and holding the reset button
Below is a list of editable parameters:
NO. PARAMETER DESCRIPTION
Gas type
02
0 = methane
1 = LPG
DHW off mode;
08
0 = fixed
1 = associated with the DHW setpoint
09
Ignition power
10
Ignition curve
LPG gas type
13
1 = propan
2 = butan
17
Complete or partial calibration
Domestic hot water modulation with flow meter
18
0 = modulation without flow meter
1 = modulation with flow meter
Water heater flow rate
0 = TTulpe C-Meister 11 P37 Eco
26
1 = TTulpe C-Meister 14 P37 Eco
2 = not available
3 = not available
27
Modulator reactivity
0 = standard water heater
28
from 1 to 20 = solar water heater, delay (in seconds)
of ignition power if requested
Any other additional parameters with respect to the table above should not be changed for any reason
Calibration menu
Pressure adjustments must be carried out by a qualified technician
Pressure adjustments must be carried out by a qualified technician
The calibration operation ends automatically after 15 minutes of
inactivity or by pressing and holding the reset button or in the
case of overheating (67°C)
RANGE
0 - 1
0 - 1
0 ... 40
0 - 3
1 - 2
0 ... 100
0 - 1
0 ... 3
0 - 1
0
from 1 to 20
Before calibration check the mains pressure, referring to the previous
paragraph.
To calibrate the gas valve (standard procedure MANU: it is possible to
deviate from the value set by approximately +/-1.5 mbar) carry out the
following operations:
Place the electric switch of the system to off
Remove the casing by unscrewing the fastening screws located at the
bottom of the water heater and detached the casing from the top
12
DEFAULT VALUE
depending on the model
0
40
1
1
0
1
depending on the model
1
0