Inverter ID : 2012041234
Self-Test OK
Testing 59.S1...
Testing 59.S2...
Testing 27.S1...
Testing 27.S2...
Testing 81>S1...
Testing 81>S2...
Testing 81<S1...
Testing 81<S2...
Advanced Function
Solar Arc Fault ON
Clear Arc_Fault
System selfcheck
DRM
Signal ISLAND MODE
BMS_Err_Stop
PassWord
X--X--X--X
1
2
4
5
7
8
CANCEL
0
Inverter ID : 2012041234
Self-Test Report
59.S1 threshold253V 900ms
59.S2 threshold264.5V
200ms
27.S1 threshold195.5V 1500ms
27.S2 threshold 34.5V
200ms
81>.S1 threshold 50.2Hz 100ms
81>.S2 threshold 51.5Hz 100ms
81<.S1 threshold 49.8Hz 100ms
81<.S2 threshold 47.5Hz 100ms
8/8
Test 59.S1 OK!
Test 59.S2 OK!
Test 27.S1 OK!
Test 27.S2 OK!
Test 81>S1 OK!
Test 81>S2 OK!
Test 81<S1 OK!
Test 81<S2 OK!
Backup Delay
0ms
Func
Set1
Gen peak-shaving
CT Ratio
2000 1
CEI 0-21 Report
DEL
3
6
9
OK
59.S1: 228V
902ms
59.S2: 229V
204ms
27.S1: 228V
1508ms
27.S2: 227V
205ms
81>.S1: 49.9Hz 103ms
81>.S2: 49.9Hz 107ms
81<.S1: 50.0Hz 95ms
81<.S2: 50.1Hz 97ms
Durante el proceso de autocomprobación, todos
los indicadores estarán encendidos y la alarma
seguirá encendida. Cuando todos los elementos de
prueba muestran OK, eso significa que la
autoprueba se completó con éxito.
Luego presione el botón "esc" para salir de esta
página. Marque "autocomprobación del sistema"
en el menú de funciones avanzadas y marque
"Informe CEI-021".
Autocomprobación del sistema: después de
marcar este elemento, debe ingresar la
contraseña.
La contraseña predeterminada es 1234.
Después de ingresar la contraseña, marque "OK"`
Esta página mostrará el resultado de la prueba de
"autocomprobación CEI-021".