12.10 Cleaning of the finned pack:
12.10.1 Place the main switch in the "OFF" position and wait until all the fans have stopped rotating. Lower the conveyor
(ref. Chapter 8). Protect the motor fans and electrical connections with waterproof covers and/or panels. If necessary,
remove the motor fans and their grilles by unscrewing the fixing screws.
12.10.2 Use compressed air at a maximum pressure of 10 bar and at a minimum distance of 150 mm, directed perpendicularly
against the finned pack to avoid bending or damage to the fins.