5
Settings
5.1
Setting the pump Calio 25-100 / Calio 40-100
▶ Observe the documents of the pumps for setting.
▶ Press the switch to activate the display from idle mode.
The display shows the current operating mode as well as alternating
electrical output and delivery rate. After 5 minutes without an entry being
made / actuation of the keys, the display switches back to idle mode.
1.
DUAL
2.
DUAL
3.
DUAL
Fig. 6
Set operating mode and adjust set value
1. To activate setting mode, press the switch for 6 seconds.
The last operating mode selected flashes ( Figure 2 [3], page 2).
2. To set the desired operating mode, turn the dial gauge until 0-10 V
lights up.
3. Press the switch to activate the operating mode selected.
The set value set is displayed by the blue circle segments illuminated
in 10 % steps.
4. Turn the dial gauge to set the set value.
5. Press the switch to accept the set value.
KSB Calio – 6721821013 (2023/03)
6s
MODBUS
0-10V
MODBUS
0-10V
MODBUS
0-10V
0010045523-001
5.1.1
Settings of the pumps on the main controllers Logamatic
5313 or CC8313
▶ Call up the service menu and navigate to the pump parameters:
Service menu > Heat source > Boiler default settings
▶ Make settings:
Pump configuration
Calio SI 25-80 HP
(main controller)
PWM
Hydraulic configuration
Pump
Modulating pump
Yes
Pump modulation w/o
On
start contact
Min. pump modulation
30 %
Pump control mode
According to output According to output
Voltage for min. flow rate 0 V
Voltage for max. flow rate 10 V
Table 2 Service settings on main controllers Logamatic 5313 or CC 8313
5.2
Setting the pump Calio SI 25-80 HP PWM
▶ Observe the documents of the pumps for setting.
▶ Press the switch ( Figure 7 [1]) to activate the display
( Figure 7 [4]) from idle mode.
The display shows the current operating mode as well as alternating
electrical output and delivery rate. After 5 minutes without an entry
being made / actuation of the keys, the display switches back to idle
mode.
4
3
Fig. 7
Settings, pump Calio SI 25-80 HP PWM
[1]
Switch change operating mode, save set value
[2]
Setting, increase set value
[3]
Setting, reduce set value
[4]
Display
Settings
Calio 25-100 /
Calio 40-100
Pump
Yes
On
30 %
0 V
10 V
x xxx xxx xxx-001
1
2
x xxx xxx xxx-001
23