Ex-AI 2xI 2-wire HART
I
(short-circuit current), max.
o
P
(output power), max.
o
C
(permissible external capacity), max. 99
o
L
(permissible external inductance),
o
max.
U
(intrinsically safe input voltage),
i
max.
U
(voltage at non-intrinsically safe
m
terminals), max.
Electrical isolation
Electrical isolation channels
Between the channels
Between the channels and the
backplane bus
Between the channels and electronics
power supply
Isolation
Isolation tested with
Isolation of field circuits to local ground
according to IEC/EN 60079-11 tested
with
Additional information
You can find more information in the certificate of the I/O module:
Ex-AI 2xI 2 wire HART, 6DL1134-6TB00-0HX1
Manufacturer
Siemens AG
Digital Industries
Process Automation
DE-76181 Karlsruhe
Ex-AI 2xI 2-wire HART
A5E50377471-AB, 03/2023
93
mA
605
mW
nF
4
mH
10
V
60
V
No
Yes
Yes
Electrical isolation between the
channels and input voltage PME
You can find more information on
insulation in the system manual
ET 200SP HA/ ET 200SP; Modules for
Devices in the Hazardous Area.
707 V DC (type test)
Ex-AI 2xI 2-wire HART
15