Outdoor Unit CU-5E34NBE
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 50Hz)
(1) Low pressure performance chart
1.2
(12.2)
1.0
(10.2)
0.8
(8.2)
0.6
(6.2)
25
30
Outdoor air temperature (°C)
(2) Operating current performance chart
12
11
10
9
8
25
30
Outdoor air temperature (°C)
(3) Indoor discharge air performance chart
25
20
15
10
5
25
30
Outdoor air temperature (°C)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
Indoor Unit CS-ME24NKE
Mid fan
Hi fan
35
40
Mid fan
Hi fan
35
40
Mid fan
Hi fan
35
40
×
1
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 50Hz)
(1) High pressure performance chart
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
-5
0
(2) Operating current performance chart
15
14
13
12
-5
0
(3) Indoor discharge air performance chart
60
55
50
45
40
35
30
25
-5
0
15
5
10
15
20
Outdoor air temperature (°C)
5
10
15
20
Outdoor air temperature (°C)
5
10
15
20
Outdoor air temperature (°C)
25
25
25